Further information for Hager ADZ366D FI-LS 3x 1P+N 6kA C-16A 30mA Type A
General
Number of poles (total)
4
Number of protected poles
3
Rated voltage
230 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
16 A
Rated fault current
0.03 A
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity Icn acc. EN 61009-1
6 kA
Disconnection characteristic
Undelayed
Surge current capacity
3 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
C
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
70 °C
Width in number of modular spacings
4
Built-in depth
70 mm
Degree of protection (IP)
IP2X
Power loss
10.9 W
Concurrently switching N-neutral
With interlocking device
Anti-nuisance tripping version
Residual current circuit breaker 3X 1P+N 6kA C-16A 30mA Type A QuickConnect. Residual current circuit breaker in accordance with DIN EN 61009-1 (VDE 0664-20) with 3 x 1-pole circuit breakers for 230 V AC circuits and a residual current protection circuit in a compact housing. QuickConnect terminal in accordance with DIN EN 60898-1 (VDE 0641-11), on the outgoing circuit up to 16 A and on the incoming circuit up to 63 A, blue test button and residual current display. Easy individual removal from the phase busbar system. Suitable for the subsequent installation of additional equipment. Labeling option directly on the device.