Further information for Hager ADM416QC RCD 4P 30mA
General
Number of poles (total)
4
Number of protected poles
4
Rated voltage
400 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
16 A
Rated fault current
0.03 A
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity Icn acc. EN 61009-1
6 kA
Disconnection characteristic
Undelayed
Surge current capacity
3 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
B
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
40 °C
Width in number of modular spacings
4
Built-in depth
70 mm
Degree of protection (IP)
IP2X
Connectable conductor cross section solid-core
25 mm²
Connectable conductor cross section multi-wired
16 mm²
Power loss
10.9 W
Concurrently switching N-neutral
With interlocking device
Anti-nuisance tripping version
Residual current circuit breaker 4P 6kA B-16A 30mA Type A QC/QB. Residual current circuit breaker in accordance with DIN EN 61009-1 (VDE 0664-20) with overload protection of the neutral conductor through a 4-pole circuit breaker for 400 V three-phase circuits and a residual current protection circuit in a compact housing. QuickConnect spring terminal in accordance with DIN EN 60898-1 (VDE 0641-11), on the outgoing and incoming circuits, blue test button and residual current display. Easy individual removal from the phase busbar assembly using top and bottom DIN rail sliders. Suitable for the subsequent installation of additional equipment. Labeling option directly on the device.