Further information for Hager ADF910D residual current circuit breaker 1P+N
General
Number of poles (total)
2
Number of protected poles
1
Rated voltage
230 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
10 A
Rated fault current
0.03 A
Leakage current type
F
Current limiting class
3
Rated short-circuit breaking capacity IEC 60947-2
6 kA
Rated short-circuit breaking capacity Icn acc. EN 61009-1
6 kA
Disconnection characteristic
Short-time delayed
Surge current capacity
3 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
B
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
40 °C
Width in number of modular spacings
2
Built-in depth
68 mm
Degree of protection (IP)
IP20
Connectable conductor cross section solid-core
25 mm²
Connectable conductor cross section multi-wired
16 mm²
Power loss
3.40 W
Concurrently switching N-neutral
With interlocking device
Anti-nuisance tripping version
Fehlerstrom-Leitungsschutzschalter 1P+N, 6kA, B-10A, 30mA, Typ F, entspricht DIN EN 61009-1 (VDE 0664-20). Ausgestattet mit QuickConnect Klemmen für schnelle Installation, unterstützt Anschlusskapazitäten von bis zu 63 Ampere am Zugang und 20 Ampere am Abgang. Integrierte blaue Test-Taste und Fehlerstromanzeige erleichtern die Überprüfung und Wartung. Ermöglicht einfache Beschriftung direkt am Gerät. Ideal für den Einsatz in Wohn- und Geschäftsgebäuden.