Further information for Hager ADA566D RCD 1P+N 30mA
General
Number of poles (total)
2
Number of protected poles
1
Rated voltage
240 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Rated current
16 A
Rated fault current
0.03 A
Leakage current type
A
Current limiting class
3
Rated short-circuit breaking capacity IEC 60947-2
10 kA
Rated short-circuit breaking capacity Icn acc. EN 61009-1
10 kA
Disconnection characteristic
Undelayed
Surge current capacity
0.25 kA
Voltage type
AC
Frequency
50 Hz
Release characteristic
C
Over voltage category
3
Pollution degree
2
Ambient temperature during operating
40 °C
Width in number of modular spacings
2
Built-in depth
68 mm
Degree of protection (IP)
IP2X
Connectable conductor cross section solid-core
25 mm²
Connectable conductor cross section multi-wired
16 mm²
Power loss
5.20 W
Concurrently switching N-neutral
With interlocking device
Anti-nuisance tripping version
Residual current circuit breaker 1P+N 10kA C-16A 30mA Type A. Residual current circuit breaker in accordance with DIN EN61009-1 (VDE 0664-20) and DIN EN 61009-2-1 (VDE 0664-21) with bi-connect terminals at the bottom, blue test button and residual current display. Easy to remove from the phase busbar system. Suitable for the subsequent installation of additional equipment. Labeling option directly on the device.