| General |
| Rated voltage | 400 V |
| Rated current | 63 A |
| Number of poles | 3 |
| Fusing screw thread | E 18 |
| Fuse reduction | adapter sleeve |
| Connection type | Frame clamp |
| Max. conductor cross-section fine-stranded | 25 mm² |
| Minimum conductor cross-section fine-stranded | 1,5 mm² |
| Max. conductor cross-section solid | 10 mm² |
| Minimum conductor cross-section solid | 1,5 mm² |
| Conductor material | Cu |
| Power dissipation per pole | 2 W |
| Rated current of circuit | 50,4 A |
| Compliance with standards | IEC 60269-3 |
| Protective measure | double insulated (protection class II) |
The ZS RS 18 fuse holder from Gustav Hensel is a 3-pole fuse element for D02 fuse inserts with a rated current of 63 A. It is specifically designed for use in fuse enclosures to supplement or replace existing installations. Mounting is done on busbars, enabling flexible and standardized integration into distribution and control enclosures. The device is part of the D0 system and is used in electrical distribution technology, particularly in installations requiring safe and reliable power distribution.
Applications
The ZS RS 18 is designed for use in installation distributors, particularly in systems manufactured in accordance with IEC 61439-3. It is suitable for wall mounting and can be installed in protected outdoor areas, provided climatic influences on the equipment are taken into account. It is used in electrical installations where individual circuits require secure protection, for example in residential and commercial buildings, industrial plants, or in distributors for lay operation (DBO). The protective measure is achieved via protective insulation (protection class II), providing additional safety.
Functions and Equipment in Detail
The fuse element has a rated voltage of 400 V and is designed for a maximum conductor cross-section of 25 mm² for fine-stranded conductors. For solid conductors, the maximum cross-section is 10 mm². Connection is made via frame terminals, suitable for connecting cables within the specified cross-sections. Conductor materials are copper (Cu), both fine-stranded and solid. The maximum number of conductors per terminal is one conductor. The power loss per pole is 2 W, indicating low heating during operation.
Technology Explained Simply
The ZS RS 18 is a fuse holder integrated into a D02 system. The designation D02 refers to the standardization of fuse inserts, ensuring standardized mounting and interchangeability. The fuse thread size is E 18, ensuring compatibility with corresponding fuse inserts. The rated current of 63 A allows use in medium to high load ranges. Conformity with IEC 60269-3 ensures compliance with international standards for fuse elements. The circuit rating is 50.4 A, which is relevant for the thermal test according to DIN EN IEC 61439-1, section 10.10.4.
Compatibility and Accessories
The holder is specifically designed for D02 fuse inserts and requires the use of fuses with thread size E 18. The adapter sleeve allows reduction of the fuse to ensure compatibility with smaller fuse inserts. Mounting on busbars enables standardization in distribution systems. Use in combination with other D0 system elements is possible to create a consistent distribution system.
Mounting and Installation
Mounting is done on busbars installed in distributors or enclosures. Frame terminals enable a secure and mechanically stable connection of the conductors. Connection cross-sections are limited to maximum values of 25 mm² (fine-stranded) and 10 mm² (solid). Conductor materials must be copper. Installation is carried out in protected areas, taking into account environmental conditions such as temperature and humidity.
Operational Advantages
The ZS RS 18 offers high reliability through compliance with IEC 60269-3 and protection class II. The low power loss of 2 W per pole ensures minimal heating, extending the service life of components. Mounting on busbars allows for quick and easy installation and interchangeability. Use in D0 systems ensures standardized and compatible integration into existing distribution systems.