| General |
| Number of changeover contacts | 2 |
| Max. continuous current | 8 A |
| Nominal voltage | 250 V AC |
| Coil voltage | 24 V DC |
| Contact material | AgNi |
| Connection type | Screw connection |
| Mounting | DIN rail 35 mm |
| Galvanic separation | 6 kV (1.2/50 μs) |
| Clearance distance | 6 mm |
| Creepage distance | 8 mm |
| Integrated functions | LED, EMC filtering |
The coupling relay of Finder's series 38, type 38.52.7.024.0050, is an electromechanical relay for mounting on a DIN rail (35 mm, according to EN 60715). It is used for galvanic isolation and signal transmission in industrial control systems, for example in enclosures, packaging machines, labelling systems or control panels. The device features two changeover contacts (2 We) with a rated current of 8 A at a rated voltage of 250 V AC. The coil voltage is 24 V DC, enabling its use in systems with direct current power supply. The contacts are made of silver-nickel (AgNi), a material known for its good conductivity and resistance to wear and oxidation.
Applications
This relay is designed for use in industrial control systems, particularly in installations requiring safe galvanic isolation between control and load circuits. Typical application areas include packaging and filling systems, traffic light controls, programmable logic controllers (PLC), and electrical distributions in enclosures. The compact form factor with 14 mm width allows for space-saving installation in standard control panels. The integrated EMC suppression and LED indicator ensure reliable signal transmission and visual status indication.
Functions and Equipment in Detail
The relay features two changeover contacts, each capable of switching a maximum continuous current of 8 A at 250 V AC. The contacts are equipped with screw terminals, ensuring a secure and mechanically stable connection. The coil operates at 24 V DC, making it suitable for use in systems with direct current power supply, such as automation technology. The integrated LED serves as a visual indicator of the coil status, while the EMC suppression minimizes network interference and enhances signal quality. The galvanic isolation between coil and contact set is 6 kV (1.2/50 μs), ensuring safe insulation even at high voltage differences.
Technology Explained Simply
Galvanic isolation is achieved through electrical insulation between the control and load sides, preventing short circuits or disturbances in the control circuit from affecting the load. The AgNi contacts ensure long service life and low contact resistance. The screw terminals allow for a secure connection that remains stable even under vibration or mechanical stress. The integrated EMC suppression reduces electromagnetic interference generated by switching the coil, thus protecting sensitive electronic components. The LED indicator shows whether the coil is energized, which is helpful during commissioning and maintenance.
Compatibility and Accessories
The relay is compatible with accessories such as the connection bridge 093.08 (8-pole, blue) for sockets 93.02/93.52, enabling parallel connection of multiple relays. The insulation plate 093.01 can be used for voltage and group separation in enclosures. Additionally, the relay 41.52.9.024.0010 (8 A, 24 V DC, 2 We, printed circuit connection) is a similar model that can be considered as an alternative in certain applications.
Mounting and Installation
The relay is mounted on a DIN rail (35 mm), with the socket equipped with a holding and removal lever that facilitates easy installation and maintenance. The screw terminals require a screwdriver to secure the wires. Installation is carried out in a closed enclosure, with ambient temperature not exceeding +70 °C. The creepage and clearance distance between input and output are 6 mm and 8 mm respectively, ensuring electrical safety.
Operational Advantages
The combination of galvanic isolation, EMC suppression, and LED indicator ensures reliable and low-maintenance operation. The screw terminals provide a mechanically stable connection that withstands industrial conditions. The use of AgNi contacts extends service life and reduces maintenance frequency. The compact design enables efficient space utilization in enclosures. The integrated EMC suppression protects the entire system from disturbances caused by switching the relay coil.