| General |
| Degree of protection | IP 20 |
| Operating voltage | 24 V AC/DC |
| Rated current | 25 A |
| Nominal voltage | 250 V AC |
| Contact material | AgSnO2 |
| Contact type | 2 make contacts (NO) |
| Coil power | 2 VA (50 Hz) |
| Operating range | 0.8…1.1 U_N |
| Holding voltage | 0.4 U_N |
| Drop-out voltage | 0.1 U_N |
| Response time | 30 ms |
| Reset time | 20 ms |
| Voltage withstand (coil/contacts) | 6 kV |
| Ambient temperature | -25…+50 °C |
| Max. switching power (AC1, 230 V AC) | 6250 VA |
| Max. switching power (AC15, 230 V AC) | 1800 VA |
| Rated current (AC3, 230 V AC) | 1 kW |
| Rated current (AC-7c) | 10 A |
| Max. power (incandescent and halogen lamps) | 2000 W |
| Max. power (LED, 230 V AC) | 200 W |
| Max. power (fluorescent lamp with electronic ballast) | 800 W |
| Max. power (fluorescent lamp with magnetic ballast) | 500 W |
| Max. power (compact fluorescent lamp) | 200 W |
| Max. switching current (DC1, 24 V) | 25 A |
| Minimum switching load | 1000 mW |
The Finder installation contactor type 22.32.0.024.4320 is an electrical switching device for use in industrial and commercial installations, specifically designed for mounting on a 35 mm support rail. It features two closing contacts and is rated for a continuous current of 25 A at a nominal voltage of 250 V AC. The device is equipped with contact material made of silver-tin oxide (AgSnO₂), which is particularly suitable for high inrush currents, for example with lamp loads. The coil is designed for an operating voltage of 24 V AC/DC and enables a hum-free actuation via alternating or direct voltage. The internal wiring ensures safe and disturbance-free operation. The protection class IP 20 provides protection against contact with fingers and against solid foreign objects, but not against water or dust, which requires indoor use.
Applications
This contactor is suitable for a wide range of applications in building and plant control, particularly in areas such as hotel room lighting, parking lot and street lighting, office and bathroom lighting control, as well as pump control. It is suitable for controlling loads such as incandescent and halogen lamps, fluorescent lamps with electronic or conventional ballasts, compact fluorescent lamps, LED lighting, and NV halogen lamps. The maximum switching capacity is 6250 VA (AC1) and 1800 VA (AC15) at 230 V AC, with the rated power for single-phase motor loads (AC3) being 1 kW. For incandescent and halogen lamps, a maximum power of 2000 W is permitted, and for LED lighting, 200 W.
Functions and Equipment in Detail
The device features a mechanical switching position indicator and an integrated LED indicator, which visually signal the operating status. The contact gap for closing contacts is at least 3 mm, ensuring reliable switching performance. The coil is equipped with a varistor at the input, serving as overvoltage protection. The reinforced insulation between coil and contacts increases electrical safety. The maximum switching capacity under DC1 operation is 25 A at 24 V, 5 A at 110 V, and 1 A at 220 V. The minimum switching load is 1000 mW (10 V / 100 mA). The mechanical life is 2 million switching operations, and the electrical life under AC-7a operation is 30,000 switching operations.
Technology Explained Simply
The contactor's coil is powered by 24 V AC or DC, actuating the contacts. The internal wiring enables hum-free operation, regardless of whether control is via alternating or direct voltage. The contact materials AgNi and AgSnO₂ are selected according to application, with AgSnO₂ being suitable for high inrush currents (up to 120 A in 5 ms). The protection class IP 20 protects against contact with fingers and solid foreign objects, but not against water or dust. The operating temperature range is between -25 °C and +50 °C.
Compatibility and Accessories
The contactor is expandable with auxiliary switches, which can be clipped on the side of the device. Compatible accessories include the auxiliary switch 022.33 (2 closing contacts, 6 A) and the auxiliary switch 022.35 (1 closing + 1 opening contact, 6 A). Additionally, a connection bridge (022.18) for up to 8 devices and a spacing piece (022.09) for mounting on the support rail are available. These components allow flexible expansion of switching functions.
Mounting and Installation
The contactor is mounted on a 35 mm support rail (according to EN 60715). The width of the device is 17.5 mm. Mounting is done by clamping onto the rail, with electrical connections made via cage terminals. The coil actuation is done via the designated connection terminals. The mechanical and LED indicators are directly visible on the device and indicate the switching status.
Operational Advantages
The contactor offers high reliability due to its robust construction and extended service life. The hum-free actuation reduces electromagnetic interference. The integrated LED and mechanical indicators facilitate maintenance and diagnostics. The expandability with auxiliary switches allows flexible adaptation to different switching requirements. Compliance with standard EN 61095:2009-11 and fire behavior standard EN 45545-2+A1:2016 for rail vehicles ensures conformity with European safety standards.