EFFEKTA Regeltechnik ZBBEFBEINBYP6301

EFFEKTA ZBBEFBEINBYP6301 Bypass Pegasus/Quasar II 3p/3p up to 30 kVA

UPS > UPS-Batteries > Original

EFFEKTA ZBBEFBEINBYP6301 Bypass Pegasus/Quasar II 3p/3p up to 30 kVA

Lieske Part No. 130082
Mfg Part No ZBBEFBEINBYP6301
EAN-Code
Manufacturer EFFEKTA Regeltechnik
Here only 635,04 EUR
755,70 EUR incl. VAT

Further information for EFFEKTA ZBBEFBEINBYP6301 Bypass Pegasus/Quasar II 3p/3p up to 30 kVA

General
Output power30 kVA
Nominal voltage400 VAC
Nominal current63 A
Mounting methodWall
Connection typeclamps
Application range3/1-phase up to 15 kVA, 3/3-phase up to 30 kVA
The item is a manual bypass from EFFEKTA Regeltechnik, designed for use in uninterruptible power supply (UPS) systems. It serves as an emergency output to supply the load directly from the mains power system in case of failure or during maintenance, without requiring the UPS to be in operation. The bypass is designed for 3/1-phase and 3/3-phase systems and supports a maximum output power of 30 kVA. The nominal voltage is 400 VAC, and the nominal current is 63 A. The unit is wall-mounted and features terminal connections for wiring.

Applications

The manual bypass is intended for UPS systems up to a power rating of 30 kVA, with the maximum power for 3/1-phase systems limited to 15 kVA. It is used in critical infrastructures where continuous power supply is required, such as data centers, medical facilities, or industrial control systems. The function allows the UPS to be temporarily taken out of service without disconnecting the connected devices from power.

Functions and Equipment in Detail

The bypass features a mechanical switching function operated manually. The switching is performed via terminal connections, ensuring a secure and reliable connection. The maximum output power of 30 kVA at 400 VAC and 63 A nominal current enables the supply of medium to large loads. The unit is designed for use in 3/3-phase systems up to 30 kVA and in 3/1-phase systems up to 15 kVA. Mounting is wall-mounted, with dimensions of 290 mm (height) × 250 mm (width) × 155 mm (depth).

Technology Explained Simply

A manual bypass bypasses the UPS unit and routes power directly from the mains supply system to the load. This is particularly useful when the UPS needs to be serviced or replaced without shutting down the connected devices. The switching is done via mechanical contacts connected through terminals. The nominal voltage of 400 VAC and nominal current of 63 A correspond to common industrial standards for medium to large UPS systems. The maximum output power of 30 kVA allows simultaneous supply of multiple devices or systems.

Compatibility and Accessories

The bypass is designed for UPS systems supporting a maximum power of 30 kVA for 3/3-phase supply or 15 kVA for 3/1-phase supply. It is specifically suitable for the Pegasus and Quasar II models from EFFEKTA, although exact compatibility with the respective UPS systems should be verified. The unit is not intended for use with other manufacturers or models unless technical specifications match.

Mounting and Installation

Mounting is done on a wall, with the unit requiring sufficient space for its dimensions of 290 mm (height) × 250 mm (width) × 155 mm (depth). Connections are made via terminals, ensuring a secure and durable connection. Installation requires compliance with electrical safety regulations, including proper earthing and use of appropriate tools. The unit is not intended for outdoor use, as no protection rating such as IP67 is specified.

Operational Advantages

The manual bypass enables continuous power supply even when the UPS is not in operation. This reduces downtime and increases the availability of critical systems. The mechanical switching is robust and does not require additional power supply. Terminal connections ensure simple and secure wiring. The unit is easy to install and does not require special tools for installation.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/130082
qrcode für EFFEKTA ZBBEFBEINBYP6301 Bypass Pegasus/Quasar II 3p/3p up to 30 kVA