Further information for Moeller 285557 PFR-5 Fi-Relay 0,03–5 A
General
Manufacturer
Eaton
Model
PFR-5
Rated control voltage
230 V AC
Frequency
50/60 Hz
Earth fault current adjustable
0,03; 0,1; 0,3; 0,5; 5 A
Delay adjustable
0,02; 0,1; 0,3; 0,5; 5 s
Auxiliary switch
1 C/O
Earth fault current early warning
Blinking red LED
Approval
not UL/CSA-approved
Pulsed current sensitive
The Eaton PFR-5 is an RCD relay designed as optional accessory for the NZM circuit breaker series. It is used for detection and response to fault currents in electrical systems and enables flexible adaptation to different applications. The device is designed for worldwide use and offers simple and flexible installation through modular function groups. It is pulse current sensitive and operates with a rated control voltage of 230 V AC at 50/60 Hz. The integrated auxiliary switch function includes a single changeover contact (1 C/O), which can be used for additional control or signaling tasks.
Applications
The PFR-5 is used in industrial and commercial installations where precise fault current monitoring is required. It is particularly suitable for installations with increased safety requirements, such as production plants, machine controls, or buildings with electrically operated systems. The modular design enables easy integration into existing NZM circuit breakers, allowing system expansion without extensive modifications.
Functions and Equipment in Detail
The relay features an adjustable fault current threshold, which can be set to values of 0.03, 0.1, 0.3, 0.5, or 5 A. These settings allow adaptation to different loads and protection requirements. Additionally, the delay time is adjustable and can be set to 0.02, 0.1, 0.3, 0.5, or 5 seconds to match the system's response time to the specific application. An early warning for increasing fault current is indicated by flashing of a red LED, enabling early diagnosis and maintenance.
Technology Explained Simply
This transformer detects the fault current in the conductor cross-section and passes it to the relay. The pulse current sensitive design ensures that even short, pulsating fault currents are detected, which is important for installations with electronic loads. The control voltage of 230 V AC is supplied via the network, eliminating the need for a separate power supply. The integrated auxiliary switch function (1 C/O) can be used for external signals or controls, for example to operate warning lights or alarms.
Compatibility and Accessories
The PFR-5 is specifically developed for the NZM circuit breaker series from Eaton and can be combined with various models of this series, including for example types NZMB1, NZMB2, NZMN1, NZMN2, NZMH1, NZMH2, NZMH3, NZMH4, N2-4-200, and N1-63-SVE. The exact selection depends on the specific application and the electrical parameters of the installation. The device is not UL/CSA approved, which must be considered when planning for markets in North America.
Installation and Mounting
Mounting is modular into the corresponding NZM circuit breakers. The modular design enables simple and quick installation without additional tools. Settings for fault current and delay time are adjusted via mechanical switches or rotary controls on the device, which are directly accessible on the relay. Wiring is done via integrated terminal clamps, designed for connection to the ring transformer and control voltage supply.
Operational Advantages
The adjustable parameters for fault current and delay time enable a customized protection function that matches the specific requirements of the installation. The early warning function via the flashing red LED increases operational safety, as fault currents are detected before the breaker trips. The modular design and easy installation reduce installation time and simplify maintenance work. Integration into the NZM circuit breaker series ensures high compatibility and system stability.