Further information for Moeller 278484 Motor Protection Switch 3-pole 6.3-10A
General
Degree of protection
IP20
Rated operating voltage
690 V
Number of poles
3
Adjustment range of overload release
6,3-10 A
Short-circuit release
14 x Iu
Mounting method
screw and snap mounting
Cap mounting dimension
45 mm
Norm
IEC/EN60947
Finger protection
according to VDE 0106 T. 100
DIN-rail
EN 50 022
Rated current
12 A
Phase failure sensitivity
Auxiliary switch
Operating indicator
The PKZM01-10 motor protection switch from Eaton is a 3-pole switch designed for use in industrial plants and machine controls. It provides electrical protection for motors and connected devices against overload and short circuit. The switch is designed in accordance with IEC/EN60947 standards and features adjustable overload tripping units as well as an instantaneous short-circuit tripping unit. It is phase-loss sensitive, meaning it reacts to the failure of a phase in a three-phase power system and disconnects the motor to prevent damage. Mounting is possible either by screwing or by snap mounting onto a DIN rail in accordance with EN 50 022, with a height of 7.5 mm or 15 mm. The mounting depth is 45 mm.
Applications
This switch is designed for use in industrial plants, machine controls, and drive technology, where reliable motor protection is required. It protects motors with a rated current of 6.3 to 10 A. The rated operational voltage is 690 V, making it suitable for applications in medium voltage ranges. The protection class IP20 ensures protection against contact with fingers and against ingress of solid foreign objects larger than 12.5 mm, but not against water or dust. Compliance with VDE 0106 T. 100 ensures finger-safe design.
Functions and Equipment in Detail
The PKZM01-10 features adjustable overload tripping units, which can be set within the range of 6.3 to 10 A. The short-circuit tripping unit is fixed at 14 times the rated current (14 × Iu). The phase-loss sensitive design reacts to the failure of a phase in the three-phase network, protecting the motor from unintended operation. An integrated auxiliary switch enables signal transmission for operating states (on/off). The operating indicator visually displays the switch status. The switches are designed for a rated current up to 12 A, with the nominal current range (Ir) specified as 6.3 to 10 A.
Technology Explained Simply
The protection function of the motor protection switch is based on monitoring the current flow in the motor. If the current rises above the set overload threshold or if a sudden short circuit occurs, the switch automatically trips and interrupts the circuit. The adjustability of the overload tripping unit allows adaptation to the specific requirements of the motor. The fixed setting of the short-circuit tripping unit at 14 times the rated current ensures a rapid response to severe faults. The phase-loss sensitive design protects against unintended operation when a phase is missing, which is particularly important for three-phase motors.
Compatibility and Accessories
Various accessories are available for this motor protection switch, which extend its functionality. These include undervoltage tripping units for different voltages (e.g. 230 V, 240 V, 24 V DC, 380 V), current-operated tripping units, insulating material enclosures (e.g. CI-PKZ01-G, E-PKZ01-G), busbar adapters (e.g. BBA0R-32, BBA0-25, BBA0-32), three-phase rail blocks (e.g. B3.2/4-PKZ0), feed-in terminals (e.g. BK25/3-PKZ0-E), wiring modules (e.g. PKZM0-XDM15ME), mechanical connection components (e.g. PKZM0-XM12DM), and side modules (e.g. BBA-XSM). These components can be combined according to application requirements to extend protection functions or optimize installation.
Mounting and Installation
Mounting is done either by screwing or by snap mounting onto a DIN rail. The rail must comply with EN 50 022, with switch heights of 7.5 mm or 15 mm. The mounting depth of 45 mm must be considered during installation planning. Installation takes place in electrical switchgear, where the switch is inserted into the motor's circuit.
Operational Advantages
The use of the PKZM01-10 provides reliable motor protection with adjustable overload and fixed short-circuit tripping units. The phase-loss sensitive design increases safety in three-phase installations. The combination of screw and snap mounting allows flexible installation. The integrated operating indicator and auxiliary switch facilitate monitoring and control during operation. Compliance with IEC/EN60947 standards and adherence to VDE 0106 T. 100 ensure safe and standardized application.