| General |
| Rated current range | 95-125 A |
| Construction size | ZB150 |
| Mounting type | Direct mounting |
| Auxiliary contacts Normally open (NO) | 1 S |
| Auxiliary contacts normally closed (NC) | 1 O |
| Phase failure sensitivity | IEC/EN 60947, VDE 0660 Part 102 |
| Degree of protection | IP00 |
| Standards and regulations | IEC/EN 60947, VDE 0660, UL, CSA |
| Functions | Test/Off button, Reset button Manual/Auto, Free release |
| Compatibility | DILM80, DILM95, DILM115, DILM150, DILM170, DILMF80, DILMF95, DILMF115, DILMF150, DIULM80, DIULM95, DIULM115, DIULM150, SDAINLM140, SDAINLM165, SDAINLM200, SDAINLM260 |
The ZB150-125 motor protection relay from Eaton is a modular component designed for use in industrial drive systems. It serves as a protection device for electric motors and is mounted directly onto contactors or reversing contactors to detect overloads, phase failures, and other disturbances, thereby protecting the motor from damage. The device is part of the ZB motor protection relay range up to 150 A and features a ZB150 size rating, designed for a nominal current range of 95 to 125 A. It is designed for direct mounting on various contactor types, including DILM80, DILM95, DILM115, DILM150, DILM170, DILMF80, DILMF95, DILMF115, DILMF150, DIULM80, DIULM95, DIULM115, DIULM150, SDAINLM140, SDAINLM165, SDAINLM200, and SDAINLM260.
Applications
This relay is used in industrial plants where electric motors are operated, particularly in production facilities, conveyor systems, pump and fan installations. It is suitable for applications requiring reliable motor monitoring to minimize downtime and extend the service life of drives. Direct mounting on the contactor enables compact and efficient integration into existing control systems.
Functions and Features in Detail
The motor protection relay includes a Test/Off button, allowing manual verification of the relay’s functionality, as well as a Reset button with Manual/Auto function to resume operation after a tripping event. The free release ensures that the relay can safely disconnect the motor even in the event of a control voltage failure or fault in the control circuit. The integrated auxiliary contacts consist of one normally closed contact (1 Oe) and one normally open contact (1 S), which can be used to control signaling or control devices.
Technology Explained Simply
The relay monitors the motor’s current consumption and responds when the set nominal current is exceeded or in the event of a phase failure. The phase failure sensitivity complies with IEC/EN 60947 and VDE 0660 Part 102 standards, ensuring reliable detection of phase faults. The protection functions are designed to avoid tripping during short-term load peaks, triggering only during sustained overloads or faults. Direct mounting on the contactor enables a mechanical and electrical connection that minimizes response time.
Compatibility and Accessories
The relay is compatible with a wide range of power contactors and reversing contactors from Eaton’s DILM, DILMF, and DIULM product families, as well as with SDAINLM contactors. Use with compatible contactors ensures safe and standard-compliant integration into the control system.
Mounting and Installation
Installation is performed directly onto the contactor, with mechanical fastening and electrical connection achieved via integrated contacts. No additional installation or wiring is required, as the relay is designed for direct mounting. The terminal clamps are intended for connection to the contactor terminals, and the auxiliary contacts can be directly integrated into the control circuit.
Operational Advantages
The motor protection relay provides reliable motor monitoring with integrated protection functions that enhance operational safety. Direct mounting reduces the number of required components and shortens response time during disturbances. The integrated auxiliary contacts allow easy connection to monitoring and signaling systems. Compliance with IEC/EN 60947, VDE 0660, UL, and CSA standards ensures conformity with international safety requirements.
Protection Rating
The device has a protection rating of IP00, meaning it is not protected against mechanical impacts or environmental conditions such as dust or moisture. It is therefore intended for use in enclosed enclosures where it is protected from external influences. The IP00 classification is typical for modular components mounted in protected environments.
Standards and Regulations
The relay meets the requirements of IEC/EN 60947, VDE 0660, UL, and CSA standards. These standards define the electrical and mechanical requirements for switching devices and ensure the device can be safely and reliably used in industrial plants. Compliance with these standards is required for approval in various markets.