| General |
| Number of poles | 4 poles |
| Connection system | Screw terminals |
| Operating voltage | 230 V |
| Frequency | 50/60 Hz |
| Utility category | AC-1, NAC-3 |
| Rated current (Ie) | 12 A |
| Thermal current (Ith) three-pole open | 22 A |
| Thermal current (Ith) three-pole encapsulated | 18 A |
| Thermal current (Ith) single-pole open | 60 A |
| Thermal current (Ith) single-pole encapsulated | 54 A |
| Rated power at 220 V/230 V | 3,5 kW |
| Rated power at 380 V/400 V | 5,5 kW |
| Rated power at 660 V/690 V | 6,5 kW |
The product is a contactor of the brand Eaton, type DILMP20(230V50/60HZ), with manufacturer number 276978. It is a 4-pole contactor designed for use in industrial installations and with 4-pole consumers. The contactors are rated for nominal currents up to 200 A and are particularly suitable for applications with non-inductive or slightly inductive loads, as well as for operating squirrel-cage motors, where category AC-1 applies to non-inductive or slightly inductive loads such as resistance furnaces, and NAC-3 is intended for starting and switching off during operation of squirrel-cage motors. The connection technique is via screw terminals, ensuring a firm and secure connection.
Applications
The contactor is intended for use in industrial electrical installations, particularly in systems with 4-pole consumers. It is used to switch electrical loads safely and reliably, with switching category AC-1 applying to resistance furnaces and other non-inductive or slightly inductive loads. Category NAC-3 enables use with squirrel-cage motors, where the contactor handles the starting process and switching off during operation. The contactors are designed for operating voltages from 220 V to 690 V, with rated power varying according to voltage: 3.5 kW at 220 V/230 V, 5.5 kW at 380 V/400 V, and 6.5 kW at 660 V/690 V.
Functions and Equipment in Detail
The contactor has 4 poles and is designed for use in 3- and 4-pole circuits. The thermal current rating (Ith) is 22 A for open construction and 18 A for enclosed construction at 40 °C in 3-pole configuration. In 1-pole configuration, the thermal current is 60 A for open construction and 54 A for enclosed construction. The nominal current (Ie) is 12 A at 380 V/400 V. The switching function is performed via screw terminals, ensuring a secure and durable connection. The operating voltage is 230 V at 50/60 Hz, suitable for most industrial applications in Europe and other regions with this frequency.
Technology Explained Simply
The contactor operates on the principle of an electromagnetic switch. When the operating voltage is applied, an electromagnet is activated, moving the switching contact and closing the circuit. When the voltage is switched off, the magnet de-energizes and the contact opens. The screw terminals allow for a mechanically stable connection that remains reliable even under high current loads. The thermal current rating (Ith) describes the maximum current the device can withstand continuously without overheating. The nominal current (Ie) is the maximum current the device can switch under normal operating conditions.
Compatibility and Accessories
The contactor can be combined with various accessories to meet specific requirements. These include auxiliary switches such as DILM32-XHI02 (2NC), DILM32-XHI11 (1NO1NC), DILA-XHI13 (1NO3NC), DILA-XHIV22 (2NO2NC), DILA-XHIT11 (1NO1NC), DILA-XHIT20 (2NO), DILA-XHI22 (2NO2NC), DILA-XHI31 (3NO1NC), DILA-XHIV11 (1NO1NC), DILA-XHIT22 (2NO2NC), as well as time modules such as DILM32-XTEE11(RA24) (0.1–100 s delayed pickup), DILM32-XTEE11(RAC130), DILM32-XTED11-100(RAC240) (5–100 s latching release), DILM32-XTEY20(RAC240) (1–30 s star-delta), DILM32-XTEE11(RAC240). Other components include the DILM32-XMAN test cube, the DILM12-XP1 parallel connector, the DILM12-XSPD diode protection circuit, the ETS4-VS3 amplifier module, and the XGKE-GE label sheet. These accessories extend the functionality of the contactor, for example by adding time delays, additional contacts, or protection functions.
Mounting and Installation
Mounting is typically done in enclosures or distribution boxes. The screw terminals allow for easy and secure connection of cables. Installation must comply with applicable regulations and standards, particularly DIN VDE 0100 and DIN VDE 0660. The contactors are designed for industrial environments and require proper installation by qualified personnel.
Advantages in Operation
The contactor offers high reliability and long service life. The screw terminals ensure a stable connection that remains intact even under high current loads. Switching categories AC-1 and NAC-3 allow use in a wide range of applications, from resistance furnaces to motors. Compatibility with various accessories enables flexible adaptation to specific requirements. The operating voltage of 230 V at 50/60 Hz is suitable for most industrial installations in Europe and other regions with this frequency. The thermal current rating and nominal current are designed for safe operation under normal conditions.