Eaton 276957, EAN: 4015082769574

Moeller 276957 Contactor 20A/AC-1 4p

Industrial Material > Industrial relays and contactors > Contactors

Moeller 276957 Contactor 20A/AC-1 4p

Lieske Part No. 351895
Mfg Part No 276957
EAN-Code 4015082769574
Manufacturer Eaton
Here only 72,65 EUR
86,45 EUR incl. VAT

Further information for Moeller 276957 Contactor 20A/AC-1 4p

General
ManufacturerEaton
Number of poles4
Operating voltage24 V
Frequency50 Hz
Rated current20 A
Utility categoryAC-1, NAC-3
Connection systemScrew terminals
Thermal current (3-pole, open)22 A
Thermal current (3-pole, encapsulated)18 A
Thermal current (1-pole, open)60 A
Thermal current (1-pole, encapsulated)54 A
Rated power (220 V/230 V)3,5 kW
Rated power (380 V/400 V)5,5 kW
Rated power (660 V/690 V)6,5 kW
The DILMP20(24V50HZ) contactor from Eaton is a 4-pole contactor designed for use in industrial installations and electrical circuits. It is intended for power consumers requiring a rated current up to 200 A, with this model having a rated current of 20 A. The operating voltage is 24 V at a frequency of 50 Hz, making it suitable for applications in control and switching systems with low voltage. The device is connected via screw terminals, ensuring a secure and stable connection. It is designed for use in the AC-1 service category, suitable for non-inductive or slightly inductive loads such as resistance furnaces, and also for the NAC-3 category, which includes operation with squirrel-cage motors, particularly during starting and switching off.

Applications
This contactor is designed for use in industrial environments where reliable and safe electrical switching is required. It is particularly suitable for installations operating with 4-pole power consumers, such as electric heaters, pumps, or motors in production facilities. The 4-pole configuration enables complete disconnection of all phases and the neutral conductor, which is essential for safe operation in three-phase networks. The contactors are designed for operating voltages from 220 V to 690 V, with rated powers varying according to voltage: 3.5 kW at 220 V/230 V, 5.5 kW at 380 V/400 V, and 6.5 kW at 660 V/690 V.

Functions and Equipment in Detail
The contactor features a conventional thermal current (Ith), which varies depending on connection type and number of poles. For a 3-pole open design, the thermal current is 22 A at 40 °C ambient temperature, and 18 A for an enclosed design. For single-pole connections, the thermal current is 60 A for open and 54 A for enclosed designs. These values are critical for thermal load capacity and selecting the appropriate switching system. The screw terminals allow for easy and secure installation, designed for connections with cables matching the respective current ratings.

Technology Explained Simply
The contactor operates using an electromagnetic coil that, when energized with the operating voltage (24 V, 50 Hz), pulls in the armature and closes the contacts, enabling current flow through the load. When the voltage is switched off, the armature drops and disconnects the contacts. The 4-pole configuration ensures that all phases and the neutral conductor are disconnected simultaneously, which is crucial for safety in electrical installations. Thermal load capacity is adjusted according to the construction type (open or enclosed) and number of poles to prevent overheating and damage.

Compatibility and Accessories
Various accessories are available for this contactor to extend its functionality. These include auxiliary switches such as the DILA-XHI20 (2S configuration) or DILM32-XHI02 (2O configuration), enabling additional switching functions. Time delay units such as the DILM32-XTED11-100(RA24) (5–100 s latching release) or DILM32-XTEE11(RA24) (0.1–100 s delayed pickup) can be used for time-controlled switching operations. Protection circuits such as the DILM12-XSPR240 (RC protection) or DILM12-XSPV48 (varistor) provide protection against voltage spikes and overvoltages. A test cube (DILM32-XMAN) allows for functional testing of the contactor.

Mounting and Installation
Mounting is done via screw terminals designed for connection with appropriate cables. The terminals are designed to ensure a secure and durable connection. Installation takes place in switch cabinets or enclosures, with ambient temperature and terminal load conditions to be considered. The open design requires sufficient cooling, while the enclosed design offers better protection against environmental influences.

Advantages in Operation
The contactor offers high reliability and safety in electrical switching. The 4-pole configuration ensures complete disconnection of circuits, which is essential for safe operation in industrial installations. The use of screw terminals enables simple and secure installation. Thermal values are matched to the respective construction type, ensuring optimal load capacity and service life. Compatibility with various accessories extends functionality and allows flexible adaptation to different requirements.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/351895
qrcode für Moeller 276957 Contactor 20A/AC-1 4p