Further information for Moeller 276705 DILM9-10(24VDC) Contactor 4kW
General
Number of poles
3-pole
Operating voltage
24 V DC
Rated operating current AC-3
9 A
Rated voltage AC-3
380/400 V
Utility category
AC-1, NAC-3, AC-4
Connection system
Screw terminals
Power
4 kW
Auxiliary switch
1S
Application range
Motors, non-inductive loads, resistance furnaces
IE3-capable
The Eaton contactor DILM9-10(24VDC) is a 3-pole contactor for use in industrial applications, particularly for controlling electric motors. It is designed for operating voltages in the range of 24 V DC and is suitable for applications with a power up to 4 kW at 400 V AC. The device is connected via screw terminals and is designed for use in control panels with a rated operational current of 9 A at AC-3 (380 V/400 V). The usage category includes AC-1 for non-inductive or lightly inductive loads, as well as NAC-3 and AC-4 for squirrel cage motors, with the latter categories covering starting, operational switching, reversing, and jogging. The contactor is also suitable for motors of efficiency class IE3, which is indicated by a specific logo on the packaging.
Applications
The contactor is primarily intended for use in industrial drive systems, particularly for controlling electric motors in machine building, material handling, and processing plants. It can be used in control panels for resistance furnaces or other non-inductive loads. The construction allows use in systems requiring high switching cycles, such as frequent starting, reversing, or jogging of motors. The rating of 4 kW at 400 V AC makes it suitable for medium motor powers in industrial environments.
Functions and Equipment in Detail
The contactor features a 3-pole main contact arrangement and is equipped with an auxiliary switch configuration of 1S (one normally open contact), making it suitable for simple status monitoring or signaling units. The connection technology uses screw terminals, ensuring a secure and mechanically stable connection. The thermal rating for AC-1 is defined as conventional thermal current, describing the load capacity under continuous operating conditions. The use of 24 V DC as operating voltage makes the device suitable for control systems in industrial automation, where this voltage is commonly used as control voltage.
Technology Explained Simply
The contactor operates on the principle of an electromagnetic switch: when the control voltage (24 V DC) is applied, an electromagnet is activated, closing the main contacts and thus enabling current flow through the load (e.g., a motor). When the control voltage is switched off, the contacts open again, interrupting the current. The switching category AC-3 refers to operation with squirrel cage motors, where the contactor can safely handle starting and switching off during operation. The rating of 9 A at 400 V AC corresponds to a power of 4 kW, representing the maximum load the device can safely switch.
Compatibility and Accessories
The contactor can be combined with various accessories that extend its functionality. These include auxiliary switches such as the DILA-XHI10-S (1S side-mountable) or DILA-XHI01-S (1NC side-mountable), enabling additional signals or safety functions. Time-delay units such as the DILM32-XTED11-10(RAC240) (0.5–10 s delayed reset) or DILM32-XTED11-100(RAC240) (5–100 s latching reset) can be used for delayed switching operations. Other options include RC protection circuits (e.g. DILM12-XSPR500) or varistors (e.g. DILM12-XSPVL48) for overvoltage protection. Mechanical interlocks (e.g. DILM12-XMV) or star point bridges (e.g. DILM12-XS1) extend the application possibilities in complex circuits.
Mounting and Installation
Mounting is carried out in standard control panels or enclosures. The screw terminals allow for simple and secure connection of the wiring. The mounting dimensions conform to the standard for modular components, enabling integration into common enclosure constructions. The use of accessories such as auxiliary switches or time-delay units requires appropriate positioning and wiring according to the technical specifications of each component.
Advantages in Operation
The contactor provides reliable switching function for medium motor powers and is designed for frequent switching operations. The use of 24 V DC as control voltage enables easy integration into existing control systems. Compatibility with various accessories allows flexible adaptation to specific requirements, such as status indication, time delay, or overvoltage protection. Suitability for IE3 motors meets current industrial requirements for energy efficiency.