| General |
| Number of poles | 3-pole - |
| Rated operating current AC-3 | 9 A |
| Operating voltage | 230V50Hz,240V60Hz - |
| Connection system | Screw terminals - |
| Utility category | AC-1, AC-3, AC-4 - |
| Nominal power | 4 kW |
| Operating voltage system | 400V AC - |
| Efficiency class | IE3 - |
| Manufacturer | Eaton - |
| Application | Power contactors for motors - |
| Switching function | start, switch off, reverse, tap - |
| Accessory compatibility | auxiliary switch, time relay, parallel connector, RC protection circuit, test cube - |
| Degree of protection | not specified - |
| Thermal current AC-1 | not specified A |
The DILM9-10(230V50HZ,240V60HZ) contactor from Eaton is a 3-pole contactor for use in industrial installations, particularly for controlling electric motors. It is designed for operating voltages of 230 V at 50 Hz and 240 V at 60 Hz, and is suitable for applications with a rated power of up to 4 kW at 400 V AC. The device is designed for use in the AC-3 duty category, which includes the control of squirrel-cage motors, particularly during starting and during switching off. It is also suitable for the AC-4 duty category, which includes additional functions such as plugging, reversing, and jogging. The connection technology uses screw terminals, ensuring a secure and mechanically stable connection. The contactor is suitable for use with motors of efficiency class IE3, with IE3 capability indicated by a logo on the packaging.
Applications
This contactor is intended for use in industrial installations, particularly in the control of electric motors. It is used in systems where a safe and reliable switching function is required, for example in manufacturing plants, conveyor systems, or pump control systems. Its use is in environments where switching functions such as starting, switching off, reversing, and jogging are required. The rating for 4 kW at 400 V AC makes it suitable for medium motor powers in industrial applications.
Functions and Equipment in Detail
The contactor features a 3-pole switching function, with the poles designed for main current circuits. The rated operational current is 9 A for AC-3 at 380 V or 400 V. The thermal loading capacity is designed for the AC-1 duty category, enabling the control of non-inductive or slightly inductive loads, such as resistance furnaces. The screw terminals provide a robust and reliable connection suitable for industrial use. The device is designed for use in systems with operating voltages of 230 V/50 Hz and 240 V/60 Hz, enabling international application.
Technology Explained Simply
The contactor operates using an electromagnetic coil, which, when energized with the operating voltage, pulls in the armature and thus closes the main contacts. The switching function is performed by mechanical contacts actuated by the movement of the armature. The screw terminals allow for a secure and durable connection of the wiring. The rating for 9 A at AC-3 and 400 V means the device is designed for operation with a specific load power that does not exceed the thermal and mechanical load capacity of the contactor. Use in combination with motors of efficiency class IE3 is possible, enabling high energy efficiency for the entire system.
Compatibility and Accessories
The contactor is compatible with various accessories that extend its functionality. These include auxiliary switches such as the DILA-XHI31 (3S1Ö), DILA-XHI13 (1S3Ö), DILA-XHI22 (2S2Ö), and the DILM32-XTEY20(RAC240) time module for star-delta switching. Other options include the DILM32-XTEE11(RAC130) time module for delayed operation functions, the DILM32-XTEE11(RA24) for 24 V AC/DC, and the DILM32-XTED11-100(RA24) for latching time functions. Additionally, parallel connectors such as the DILM12-XP1 and RC protection circuits such as the DILM12-XSPR240 are available to extend protection functions. Test blocks such as the DILM32-XMAN allow for testing the contactor’s functions.
Mounting and Installation
Mounting is carried out in standard control panels or enclosures. The screw terminals allow for easy and secure connection of the wiring. Electrical connections are made via the main contacts and auxiliary contacts, with wiring according to the technical documentation. Mechanical mounting is done via designated mounting points, ensuring secure fixation in the enclosure. Installation must comply with applicable standards and regulations for electrical installations.
Advantages in Operation
The contactor provides a reliable and safe switching function for industrial applications. The use of screw terminals ensures a mechanically stable connection that remains secure even under vibration and mechanical stress. The rating for 9 A at AC-3 and 400 V enables use in a wide range of applications. Compatibility with various accessories extends functionality and allows individual adaptation to specific requirements. Suitability for motors of efficiency class IE3 supports the energy efficiency of the entire system.