| Features |
| Breaking capacity | 30000 A |
| Number of poles | 3 |
| International Protection (IP) code | IP20 |
| Pollution degree | 3 |
| Product colour | Black, White |
| Certification | IEC/EN 60947 |
| Operational conditions |
| Operating temperature (T-T) | -25 - 70 °C |
| Storage temperature (T-T) | -40 - 70 °C |
| Power |
| Rated current | 80 A |
| Weight & dimensions |
| Width | 90 mm |
| Depth | 88 mm |
| Height | 145 mm |
The NZMB1-M80 circuit breaker from Eaton is a compact switching device for use in the IEC market, designed for the protection of electrical installations and motors. With a rated current of
80 A and a switching capacity of
30000 A, it provides a robust solution for industrial applications. The device features
3 poles and is available in black and white. The protection rating
IP20 ensures protection against contact with fingers and against solid foreign objects, but not against splashing water or dust – suitable for indoor use under normal operating conditions. The operating temperature ranges from
-25 °C to 70 °C, and the storage temperature ranges from
-40 °C to 70 °C. Dimensions are
90 mm (width) × 88 mm (depth) × 145 mm (height).
Applications
The NZMB1-M80 is designed for use in industrial and commercial electrical installations, particularly for protection and control tasks involving motors and electrical loads. It meets switching category
AC-3 according to IEC/EN 60947-2, confirming its suitability for motor starting and stopping operations. The modular design enables flexible mounting in enclosures and distributions.
Functions and Equipment in Detail
The switch is equipped with a
thermal-magnetic trip unit that detects and interrupts both thermal overloads and magnetic short-circuit currents. The trip class is
10 A, enabling rapid response to overloads. The
phase failure sensitivity ensures the switch trips if one phase fails, protecting the motor from damage. Certification to
IEC/EN 60947 ensures compliance with international standards for circuit breakers.
Technology Explained Simply
The thermal-magnetic trip unit combines two protection principles: the thermal component reacts to sustained overloads by tripping the switch via thermal expansion, while the magnetic component responds immediately to high short-circuit currents to prevent damage. The switching capacity of 30000 A demonstrates the device’s ability to safely interrupt high current surges. The IP20 protection rating is suitable for indoor environments where there is no direct moisture or dust exposure.
Compatibility and Accessories
Various accessories are available to extend functionality. These include
under-voltage release units such as NZM1-XUL208-240AC or NZM1-XUL380-440AC, which trip the switch during voltage dips.
Rotary handles such as NZM1-XDV or NZM1-XTVDV allow for secure, lockable operation. Additionally,
main switch kits such as NZM1-XSRM-L or NZM1-XSR-L and
insulating housing units such as NZM1-XCI43/2-TVDVR are available. For mounting in enclosures,
tunnel terminals such as NZM1-XKAM are also offered. The use of
external warning signs such as ZFS61-NZM7 or ZFS62-NZM7 supports device identification.
Mounting and Installation
The modular construction of the NZMB1-M80 allows for flexible mounting in standard enclosures. Its compact size enables multiple devices to be installed in limited space. Mounting is typically done via screw fastening in the enclosure. Connections are made using the integrated terminal clamps, with maximum cross-sections to be observed according to technical specifications.
Operational Advantages
The NZMB1-M80 provides reliable protection for motors and electrical loads. The modular design reduces installation time and allows individual adaptation to specific applications. Compliance with standards IEC/EN 60947-2 and IEC/EN 60947-4-1 ensures compatibility with other components and operational safety. Phase failure sensitivity increases system reliability, especially for motors that can be damaged by incomplete phase supply.