| Features |
| Circuit breaker type | Miniature circuit breaker |
| Breaking capacity | 10000 A |
| Number of poles | 2 |
| International Protection (IP) code | IP20 |
| Pollution degree | 2 |
| Operational conditions |
| Operating temperature (T-T) | -25 - 40 °C |
| Power |
| Rated current | 16 A |
| Rated voltage | 240 V |
| Weight & dimensions |
| Depth | 69.5 mm |
The product is a residual current circuit breaker with overload protection, also known as an RCBO (Residual Current Breaker with Overload protection), manufactured by Eaton, type PXK-B16/1N/003-A. It ensures electrical safety in residential and commercial installations by automatically disconnecting the circuit in case of overload or detection of a fault current. The device is designed for use in installation enclosures and provides protection against electric shock as well as overload and short-circuit conditions. It has a rated current of 16 A and is designed for a nominal voltage of 240 V.
Residual current circuit breaker with integrated line protection switch (LS) enables a compact and efficient protection solution. The switch features a Type B tripping characteristic, typical for applications with medium loads, such as those found in apartments, offices, or small commercial businesses. The rating is according to IEC/EN 61009, with a rated switching capacity of 10 kA. This means the device is capable of safely interrupting a short-circuit current of up to 10,000 amperes, which is sufficient for use in residential and commercial electrical installations.
Technology explained simply – The switch detects fault currents as low as 30 mA (0.03 A) and trips immediately to minimize the risk of electric shock. Fault current detection is Type A, meaning the switch reliably detects pulsating fault currents, such as those occurring with devices equipped with electronic power supplies. The switching capacity of 10000 A ensures reliability under high current loads. The protection class IP20 protects against finger contact and solid foreign objects, but not against water or dust – therefore, the device is intended for indoor use only.
Applications – The device is suitable for use in residential buildings, office buildings, and small commercial facilities. It is mounted in electrical distribution enclosures or installation boxes to protect individual circuits, such as those for lighting, sockets, or appliance connections. The operating temperature range is between -25 °C and +40 °C, allowing use in normal indoor environments as well as in lightly climate-controlled outdoor areas (e.g., in enclosures).
Compatibility and accessories – The device is part of Eaton’s PXK series and can be mounted in standard installation enclosures with modular mounting systems. It is suitable for use in switchgear systems according to IEC/EN 61439. The power loss is 3.6 W per device, with the values for power loss per pole and static being 0 W each. The impulse withstand current is specified as 250 A, indicating the mechanical withstand capability during short-circuit events.
Mounting and installation – The switch is designed for modular mounting and is installed in standard installation enclosures with a 18 mm module width. The depth is 69.5 mm, which must be considered when planning the enclosure depth. Mounting is done via screw connections, with conductors connected from the outside. The mechanical function is ensured as long as the manufacturer’s installation instructions are followed.
Operational advantages – The combination of residual current and overload protection in a single device reduces space requirements in the distribution box and simplifies installation. The high switching capacity and reliable fault current detection ensure safe operation. Compliance with standards IEC/EN 61009 and IEC/EN 61439 guarantees compatibility with other components in the switchgear system. The operating temperature range of -25 to +40 °C allows flexible use in various environments.