Eaton 236805, EAN: 4015082368050

Moeller 236805 PXF-63/4/05-A residual current circuit breaker 4-pole 63A

Installation > Modular devices / equipment installation > RCD

Moeller 236805 PXF-63/4/05-A residual current circuit breaker 4-pole 63A

Lieske Part No. 397402
Mfg Part No 236805
EAN-Code 4015082368050
Manufacturer Eaton
Here only 201,14 EUR
239,36 EUR incl. VAT

Further information for Moeller 236805 PXF-63/4/05-A residual current circuit breaker 4-pole 63A

Features
Circuit breaker typeResidual-current device
Breaking capacity10000 A
Number of poles4
International Protection (IP) codeIP20
Pollution degree2
Operational conditions
Operating temperature (T-T)-25 - 40 °C
Storage temperature (T-T)-35 - 60 °C
Power
Rated current63 A
Rated voltage400 V
Weight & dimensions
Width70 mm
Depth70.5 mm
Height80 mm
The residual current circuit breaker PXF-63/4/05-A from Eaton is a 4-pole circuit breaker designed for use in electrical distributions in residential buildings as well as in commercial installations. It is specifically designed for protecting circuits against dangerous earth fault currents and offers a rated short-circuit withstand capacity of 10,000 A. The breaker features a rated current of 63 A and is designed for a rated voltage of 400 V, making it suitable for typical three-phase installations in buildings. The protection class IP20 ensures protection against contact with fingers and against solid foreign objects, but not against splashing water or dust – therefore, it is intended for use indoors under normal operating conditions.

Applications
This circuit breaker is intended for use in residential and commercial buildings where high safety standards for electrical installations are required. It protects people and equipment against dangerous earth fault currents that may arise from insulation faults or short circuits. The 4-pole design enables protection of three-phase circuits with a neutral conductor, which is common in modern distributions. The operating temperature range of -25 °C to 40 °C makes the breaker suitable for use in locations with climatic variations, while the storage temperature range of -35 °C to 60 °C allows for flexible storage.

Functions and Features in Detail
The breaker is designed as a residual current circuit breaker (RCCB) and detects earth fault currents starting at a rated residual current of 0.5 A. This value is sufficient for protection against dangerous touch voltages and meets the requirements for residential and office installations. The switching capacity of 10,000 A protects the breaker against thermal and mechanical stress during short-circuit events. The Type A design enables detection of pulsating earth fault currents, which may be generated by electronic devices.

Technology Explained Simply
The circuit breaker operates on the principle of differential current measurement: it compares the current entering the conductors with the current returning. If a difference exceeding the set residual current of 0.5 A occurs, the breaker trips within milliseconds and disconnects the circuit. The 4-pole construction ensures that all conductors (three phases and one neutral conductor) are switched off simultaneously, ensuring safe disconnection. The protection class IP20 protects against contact with fingers and solid foreign objects, but is not suitable for damp or dusty environments.

Compatibility and Accessories
The breaker is designed for installation in standard installation enclosures and fits into standard mounting rails with a width of 70 mm. Dimensions are 70 mm (width), 70.5 mm (depth), and 80 mm (height), enabling compact installation in distributions. It is designed for use in distributions with a rated voltage of 400 V and can be used in combination with other devices from the Eaton PXF program to ensure a uniform installation system.

Installation and Mounting
Mounting is carried out in standard distribution enclosures or boxes using mounting rails. The mounting width of 70 mm corresponds to the standard for modular devices. Installation requires compliance with applicable regulations for electrical installations, particularly VDE 0100 and DIN VDE 0664. The breakers are intended for indoor installation, as protection class IP20 does not provide protection against moisture or dust.

Operational Advantages
The circuit breaker provides reliable protection against dangerous earth fault currents, safeguarding people and electrical installations. The high switching capacity of 10,000 A ensures safe operation even under high short-circuit currents. The 4-pole design enables safe disconnection of three-phase circuits, and Type A detection ensures recognition of pulsating earth fault currents that may occur with modern electronic devices. The compact design facilitates installation in distributions with limited space.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/397402
qrcode für Moeller 236805 PXF-63/4/05-A residual current circuit breaker 4-pole 63A