| Features |
| Circuit breaker type | Residual-current device |
| Breaking capacity | 10000 A |
| Number of poles | 2 |
| Pollution degree | 2 |
| Operational conditions |
| Operating temperature (T-T) | -25 - 40 °C |
| Storage temperature (T-T) | -35 - 60 °C |
| Power |
| Rated current | 25 A |
| Rated voltage | 230 V |
| Weight & dimensions |
| Width | 35 mm |
| Depth | 70.5 mm |
| Height | 80 mm |
The residual current circuit breaker PXF-25/2/003-A from Eaton is a 2-pole circuit breaker for use in electrical installations in residential areas as well as in commercial applications. It is specifically designed to quickly and safely interrupt the power supply in the event of fault currents, for example due to insulation faults or contact with conductors. The breaker has a rated current of 25 A and is designed for a nominal voltage of 230 V, making it suitable for typical single-phase AC installations in buildings. The switching capacity is 10000 A, ensuring high short-circuit resistance and thus safe disconnection at high current levels.
Residual current circuit breakers are central components in electrical safety systems, as they disconnect within milliseconds at a fault current of 0.03 A (30 mA). This value corresponds to the
rated residual current IΔN and is standard for protection against electric shocks and fire hazards in residential and office buildings. The breaker is designed as
Type A, meaning it can detect and disconnect both alternating and direct current fault currents, making it suitable for applications with electronic devices or rectifiers.
Applications include installation in apartments, offices, commercial enterprises, and other facilities where high electrical safety is required. The breaker is designed for mounting in standard installation switchboards that support a module width of 35 mm. Dimensions are 35 mm (width), 70.5 mm (depth), and 80 mm (height), enabling compact installation in typical distribution boxes. The operating temperature ranges from -25 °C to 40 °C, ensuring reliable operation even in rooms with cooler or warmer ambient conditions. For storage, a temperature range of -35 °C to 60 °C is permitted.
Functions and equipment in detail include the ability to detect fault currents from 30 mA and disconnect within a maximum of 40 milliseconds, ensuring protection for people and equipment. The
switching capacity of 10000 A ensures that the breaker is not damaged even at high short-circuit currents and that the power supply is safely interrupted. The
pollution degree class 2 means the breaker is suitable for environments where no strong contamination or aggressive chemicals occur, such as in typical residential or office buildings.
Technology explained simply shows that the breaker features an electromechanical tripping mechanism activated by a magnetic or electromagnetic sensor upon detection of a fault current. Disconnection occurs via mechanical contact separation, interrupting the current flow. The design ensures high reliability and longevity, even with frequent operation. Installation is in standard installation switchboards with 35-mm module width, meeting VDE and DIN standards.
Compatibility and accessories include use in combination with other devices from Eaton's PXF series, particularly in distribution boxes designed for mounting 35-mm modules. The breaker is designed for use in single-phase networks with 230 V and can be integrated in a distribution box together with other protective devices, such as surge protection devices or load switches.
Installation and mounting takes place in standard electrical distribution boxes offering mounting space for 35-mm modules. Mounting conditions comply with common standards for installation devices. Mounting does not require special tools, but compliance with electrical safety regulations and correct wiring according to VDE 0100 is mandatory. The breaker is intended for installation in enclosed distribution boxes, with ambient temperature within the specified range.
Operational advantages lie in the high safety provided by rapid disconnection at fault currents. The high switching capacity of 10000 A ensures reliable operation even under high current loads. The compact design enables efficient use of space in distribution boxes. The breaker is designed for use in residential and commercial installations, making it suitable for many standard installations. The operating temperature range ensures functionality even in rooms with varying ambient conditions.