| Features |
| Circuit breaker type | Miniature circuit breaker |
| Breaking capacity | 10000 A |
| Number of poles | 1 |
| International Protection (IP) code | IP20 |
| Pollution degree | 2 |
| Operational conditions |
| Operating temperature (T-T) | -25 - 55 °C |
| Power |
| Rated current | 10 A |
| Rated voltage | 230 V |
| Weight & dimensions |
| Depth | 70.5 mm |
The PXL-C10/1 circuit breaker from Eaton is a
miniature circuit breaker with a rated current of 10 A and a rated voltage of 230 V. It is designed for use in residential buildings as well as in commercial installations and serves to protect electrical circuits against overload and short-circuit. The breaker features a
C-characteristic, suitable for applications with medium to high inrush currents, such as those occurring with electric motors or heating appliances. The
breaking capacity is 10000 A, corresponding to the rated breaking capacity according to IEC/EN 60898-1, ensuring safe disconnection under short-circuit conditions.
Applications
The breaker is intended for use in electrical installations in residential buildings as well as in small and medium-sized commercial facilities. It protects individual consumer circuits or groups of consumers with a maximum current consumption not exceeding 10 A. The
IP20 protection rating provides protection against contact with fingers and against solid foreign objects, but not against splashing water or dust – therefore, it is suitable exclusively for indoor installations. The operating temperature ranges from -25 °C to +55 °C, allowing use in normal indoor environments as well as in slightly climate-controlled or uninsulated rooms.
Functions and Equipment in Detail
The breaker is
1-pole, meaning it protects a single circuit (e.g., the live conductor). The C tripping characteristic ensures that the breaker does not trip at currents up to approximately 5 times the rated current (i.e., up to 50 A), but only at higher currents indicating a short-circuit or severe overload. This prevents unnecessary disconnection during normal inrush currents. The
depth of the device is 70.5 mm, which must be considered when planning installation in enclosures or distribution boxes.
Technology Explained Simply
A
miniature circuit breaker such as the PXL-C10/1 operates electromechanically: during overload, a bimetal strip heats up and triggers the breaker after a certain time. In the event of a short-circuit, a very high current activates an electromagnet that immediately disconnects the breaker. The
breaking capacity of 10000 A indicates how much energy the breaker can safely interrupt during a short-circuit without damage. The IEC/EN 60898-1 standard defines the requirements for performance and safety of circuit breakers.
Compatibility and Accessories
The breaker is designed for installation in standard distribution boards and enclosures. Suitable accessories include the
Euro-Vario busbar designated EVG-16/3PHAS/12MODUL (part number 291472), which is suitable for mounting multiple breakers in a row. This busbar enables structured and secure interconnection of breakers and is rated for a nominal current of 100 A.
Mounting and Installation
The breaker is mounted on standard installation rails (e.g., DIN rails). Installation is done by simply snapping the device into the rail, with the depth of 70.5 mm needing to be considered when planning the enclosure depth. Wiring is done via the terminals at the connection points, designed for secure and durable connections. Installation should be carried out in accordance with applicable regulations and standards (e.g. VDE 0100).
Operational Advantages
The breaker provides reliable protection against overload and short-circuit, safeguarding electrical systems from damage. The C-characteristic ensures appropriate response to inrush currents, increasing the availability of electrical supply. The
IP20 protection rating ensures safe operation indoors, and the high breaking capacity of 10000 A ensures robust and long-lasting performance under normal operating conditions.