| Features |
| Circuit breaker type | Miniature circuit breaker |
| Breaking capacity | 10000 A |
| Number of poles | 1 |
| International Protection (IP) code | IP20 |
| Pollution degree | 2 |
| Operational conditions |
| Operating temperature (T-T) | -25 - 55 °C |
| Power |
| Rated current | 13 A |
| Rated voltage | 230 V |
| Weight & dimensions |
| Depth | 70.5 mm |
The circuit breaker
PXL-B13/1 from
Eaton is a
miniature circuit breaker with a rated current of
13 A and a nominal voltage of
230 V. It is designed for use in
residential areas as well as in
commercial applications and provides reliable protection against overloads and short circuits in electrical circuits. The breaker features a
trip characteristic B, suitable for installations with medium loads and typical consumers such as lighting, heating, or small electrical appliances. It is
1-pole, making it intended for protecting individual circuits in single-phase networks.
Applications
The breaker is intended for use in
indoor installations, particularly in apartments, offices, shops, and other non-public facilities. It is designed for mounting in
modular enclosures or
enclosures and is suitable for standard installations in electrical and installation construction. The application is in electrical systems executed according to the standards
IEC/EN 60898-1, with the breaker having a
rated switching capacity of 10 kA. This ensures that it can safely disconnect even under high short-circuit currents and protect the system.
Functions and Equipment in Detail
The breaker operates based on a
thermal-magnetic tripping mechanism. The thermal component reacts to sustained overloads by deforming a bimetal strip due to heat generation, which disconnects the breaker. The magnetic component ensures immediate disconnection in case of sudden, high current surges (short circuit). The
trip characteristic B means that the breaker disconnects within seconds at a current of approximately 3 to 5 times the rated current (i.e., 39 to 65 A), which is optimal for typical residential and office installations.
Technology Explained Simply
At temperatures above +55 °C, the current-carrying capacity decreases linearly by 0.5 % per degree Celsius. The
protection class IP20 means that the breaker is protected against contact with fingers and against solid foreign objects with a diameter of at least 12.5 mm. However, it is not suitable for outdoor use or in damp environments, as it is not waterproof. The
pollution degree 2 indicates an environment with low pollution, typical for indoor spaces.
Compatibility and Accessories
The breaker is intended for mounting in standard installation enclosures and boxes. It is compatible with the
Euro-Vario busbar EVG-16/3PHAS/12MODUL (part number 291472), which enables a secure and standardized connection. This busbar is rated for a nominal current of 100 A and is suitable for multi-pole installations. The mounting depth of the breaker is
70.5 mm.
Mounting and Installation
Mounting is carried out in standard installation boxes or enclosures. The breaker is inserted into the designated rails or holders and locked in place. Connections are made via the terminals at the ends of the device, with connections to the conductors to be made in accordance with the regulations of the respective installation standards. The manufacturer’s installation instructions must be observed to ensure mechanical functionality.
Advantages in Operation
The breaker offers high reliability and safety in daily use. The
rated switching capacity of 10 kA ensures safe disconnection even under high short-circuit currents. The
trip characteristic B is optimally matched for most residential and office installations. The
IP20 protection class provides sufficient protection against mechanical damage and contact, although application is limited to indoor environments. Compliance with the standard
IEC/EN 60898-1 ensures conformity with European safety standards. The power loss is
2.5 W per pole, which is relevant for heat generation during operation.