| General |
| Rated control voltage | 60 V DC |
| Operating range x factor US | 0,85-1,1 |
| Max. operating current | 3 A |
| Max. inrush current (35 ms) | 15 A |
| Max. power AC/DC | 150 VA/W |
| Max. starting power (35 ms) AC/DC | 3 VA/W |
| Maximum switching frequency per minute | 3 |
| Switching frequency of circuit breaker | 60 /h |
| Suitable for | IZMX16, INX16 |
The article
Eaton +IZMX-M16-60DC-1 is a motor drive as additional equipment for circuit breakers of types IZMX16 and INX16. It is used for the automatic tensioning of the spring-energy storage mechanism to enable remote or local operation of the switch. The drive is specifically designed for industrial applications where reliable and remotely controlled switch operation is required, for example in automation systems or for controlling electrical loads in production facilities.
Applications
The motor drive is intended for use in industrial electrical installations, particularly in conjunction with circuit breaker types IZMX16 and INX16. It enables remote control of the switch position, which is advantageous when integrating into higher-level control and monitoring systems. The automatic tensioning of the spring-energy storage mechanism ensures that the switch can be operated at any time without requiring manual pre-tensioning. This is particularly important in installations with high switching frequencies or in hard-to-reach installations.
Functions and Equipment in Detail
The drive operates with a rated control voltage of
60 V DC. The operating range lies within a factor of 0.85 to 1.1 of the nominal voltage, allowing a tolerance of ±15 % relative to the nominal voltage. This ensures stable operation even with slight voltage fluctuations in the network. The maximum operating current is
3 A, while the maximum starting current (within 35 ms) can reach
15 A. The maximum power is
150 VA/W for AC/DC, with the maximum starting power (35 ms) being
3 VA/W. These values are relevant for dimensioning the supply lines and protective devices.
Technology Explained Simply
The motor drive uses an electric motor to automatically tension the spring-energy storage mechanism of the switch. This mechanism stores the energy required for switch operation, enabling fast and reliable switching. Remote or local operation is achieved via a control signal that activates the motor. The maximum switching frequency is
3 switching operations per minute, while the overall switching frequency of the circuit breaker is
60 switching operations per hour. This is an important parameter for assessing the load capacity and service life of the drive in continuous operation.
Compatibility and Accessories
The motor drive is specifically designed for circuit breaker types
IZMX16 and
INX16. It is not suitable for other switch types, as the mechanical and electrical interface is tailored to these models. Use with other devices is not intended and may result in malfunctions.
Mounting and Installation
Mounting is done directly onto the IZMX16 or INX16 circuit breaker. The drive is mechanically attached to the switch unit and electrically connected to the control voltage supply. The electrical connection is made via the designated terminal clamps, which are designed for a voltage of 60 V DC.
Advantages in Operation
The use of the motor drive enables remote operation of the switch, simplifying maintenance and control of electrical installations. The automatic tensioning of the spring-energy storage mechanism reduces manual effort and increases operational safety. The high switching frequency and robust construction make the drive suitable for industrial applications where reliability and long-term operation are required. The operating voltage of 60 V DC is common in many industrial control systems, facilitating integration.