Further information for Moeller 170708 residual current circuit breaker 1p+N 32A
General
Rated fault current
30 mA
Rated current
32 A
Release characteristic
B
Rated switching capacity
10 kA
Number of poles
1 p+N
Operation temperature
-25 °C
Latching slider
tristable
Accessory compatibility
ZP-NHK, ZP-IHK, ZP-ASA/230, ZP-WHK, ZP-ASA/24
Terminal rear insertion protection
The residual current circuit breaker / line circuit breaker combination type FRBMM-B32/1N/003-A from Eaton is a compact, mains-voltage-independent switching device for use in installations with increased safety requirements. It combines the functions of a residual current circuit breaker (RCCB) with those of a line circuit breaker (LCB) in a single housing and is specifically designed for use in construction power and outdoor distribution systems. The device is suitable for operating temperatures down to -25 °C and can therefore also be used outdoors. The combination enables efficient protection against electric shock and short circuits in a single component.
Applications
The FRBMM-B32/1N/003-A is designed for use in industrial, commercial, and construction site installations, particularly in environments with increased humidity or dust risk. It is suitable for applications in outdoor distribution boxes, construction power distributors, and other outdoor installations where reliable protection is required under harsh conditions. The operating temperature down to -25 °C also makes it suitable for cold regions or seasonal construction sites.
Functions and Equipment in Detail
The device features a contact position indicator in red-green, which visually indicates the status of the switch (on/off). A terminal rear-access protection prevents accidental contact with terminals and increases safety during maintenance. The tristable latching slider allows the device to be removed from an existing mounting system without damaging the installation. The device is equipped with a rated residual current of 30 mA, which is standard for protection against electric shock in residential and office areas as well as in construction site installations. The rated current is 32 A, with the series available up to 40 A. The tripping characteristic is assigned to curve B, which is typical for residential and small installations.
Technology Explained Simply
The combination of residual current and line circuit breaker ensures that both overloads (due to excessive current) and fault currents (e.g., due to insulation faults) are detected and switched off. The mains-voltage-independent function means that the switch remains operational even during voltage drops or outages, which is particularly important in construction site installations. The rated switching capacity of 10 kA indicates the maximum energy the device can safely interrupt during a short circuit without damage. The protection rating is not explicitly stated, but use outdoors and at temperatures down to -25 °C indicates a robust design meeting the requirements for outdoor installations.
Compatibility and Accessories
The device can be retrofitted with various accessories to activate additional functions. These include, for example, the ZP-NHK tripping signal switch 2W, the ZP-IHK auxiliary switch 1S1Ö, the ZP-ASA/230 load tripping device for voltages of 110–415 V AC, the ZP-WHK auxiliary switch 1W, and the ZP-ASA/24 load tripping device for 12–110 V AC. These accessories extend functionality, such as providing signaling devices or additional contacts for control systems.
Mounting and Installation
The FRBMM-B32/1N/003-A is designed for modular installation in standard distribution boxes. Mounting is carried out in the usual way within a mounting system, with the tristable latching slider enabling safe removal from existing installations. The terminals are designed for connection to cables, with the rear-access protection increasing safety during installation. Installation requires no special tools or additional components beyond those already integrated in the device.
Advantages in Operation
The combination of RCCB and LCB functions in a single device reduces space requirements in the distribution box and simplifies planning and maintenance. The mains-voltage-independent function ensures high reliability, especially in environments with unstable voltage conditions. The contact position indicator facilitates visual monitoring of the operating status, and the extensive accessory program allows flexible adaptation to specific requirements. The operational capability down to -25 °C extends the application range to climatically demanding regions.