| Circuit breaker type | Residual-current device |
| Breaking capacity | 10000 A |
| Number of poles | 4 |
| International Protection (IP) code | IP20 |
| Pollution degree | 2 |
| Operational conditions |
| Operating temperature (T-T) | -25 - 50 °C |
| Storage temperature (T-T) | -35 - 60 °C |
| Power |
| Rated current | 40 A |
| Rated voltage | 415 V |
| Weight & dimensions |
| Width | 70 mm |
| Depth | 70.5 mm |
| Height | 80 mm |
The FRCDM-40/4/003-G/B residual current circuit breaker from Eaton is a 4-pole circuit breaker for industrial and extended commercial applications. It is designed for a rated current of 40 A and protects electrical installations against dangerous fault currents. The breaker features a rated short-circuit withstand capacity of 10 kA, with the indication “with pre-fuse kA” indicating that the short-circuit withstand capacity applies under the condition of a preceding fuse. The rated voltage is 415 V, making it suitable for use in three-phase networks typically found in industrial environments. The rated residual current is 0.03 A (30 mA), indicating high sensitivity to fault currents and being important for the protection of personnel and installations in sensitive environments.
Applications
This circuit breaker is designed for use in industrial installations and extended commercial environments where high safety and reliability are required. It is particularly suitable for installations where electrical devices and machines with high energy demand are operated. The protection class IP20 ensures protection against contact with fingers and against solid foreign objects, but not against water or dust. This makes the breaker suitable for indoor use where no special environmental conditions such as humidity or contamination are present.
Functions and Equipment in Detail
The breaker is designed as a universal residual current circuit breaker, meaning it can detect and switch off both alternating and direct current fault currents. This is particularly important in installations with electronic devices that may generate direct current fault currents. The switching capacity of 10000 A demonstrates the device’s ability to safely switch high current levels. The operating temperature ranges from -25 °C to 50 °C, enabling use in indoor environments with varying climatic conditions. For storage, a temperature range of -35 °C to 60 °C is permissible.
Technology Explained Simply
The circuit breaker operates on the principle of residual current protection: it monitors the current flow in all conductors and trips when an imbalance between incoming and outgoing current is detected, indicating a fault current. The sensitivity of 0.03 A allows for a rapid response to dangerous currents that could harm people or equipment. The 4-pole design covers all conductors (three phases and neutral conductor), which is necessary for complete protection in three-phase systems.
Compatibility and Accessories
Various accessories are available to extend functionality. These include the re-closing device Z-FW-LP (230 VAC), the remote test module Z-FW/003 (0.03 A), the remote switching module Z-FW-MO (ON/OFF/TEST), and the re-closing device set Z-FW-LP/MO. Additionally, the auxiliary switch Z-HK (1NO1NC) and the trip signal switch Z-NHK (2W) are available. These modules enable remote control, remote monitoring, or integration into higher-level control systems. The mentioned accessories are specifically designed for use with the FRCDM-40/4/003-G/B.
Mounting and Installation
The circuit breaker is designed for panel mounting and has a width of 70 mm, depth of 70.5 mm, and height of 80 mm. These dimensions conform to the standard for switchboards and allow for easy installation in existing enclosures. Mounting is carried out in the usual manner for panel-mounted devices, with electrical connections to be made according to regulations and the specific application.
Advantages in Operation
The use of the FRCDM-40/4/003-G/B provides high safety through detection and disconnection of fault currents as low as 0.03 A. The high switching capacity of 10000 A and the 4-pole design ensure reliable operation in complex electrical installations. Compatibility with various accessory modules extends functionality and enables flexible integration into existing systems. The operating temperature range of -25 °C to 50 °C ensures stable performance under a wide range of indoor conditions.
Residual current circuit breaker,
universal residual current protection,
4-pole,
IP20,
rated current 40 A,
rated residual current 0.03 A