Further information for Moeller 106788 LS-S11/P position switch 1S1Ö roller actuator
General
Degree of protection
IP66, IP67
Ambient temperature
-25 - +70 °C
Construction type
EN 50047 Form C
Contacts Normally open (NO)
1
Contacts Normally closed (NC)
1
Colour of housing cover
Yellow
Housing
Plastic
Connection type
Screwed terminal
Standards and regulations
IEC/EN 60947
Forced opening
The Eaton position switch type LS-S11/P is a mechanical end switch for industrial applications, designed as a safety position switch with forced opening function. It is used for the detection of motion states or positions in machines and plants, particularly in environments where reliable and safe switching function is required. The switch features a roller plunger and is supplied as a complete unit, allowing direct integration into existing systems. The design conforms to standard EN 50047 form C, enabling standardized mounting and wiring.
Applications
The LS-S11/P is suitable for use in industrial automation technology, particularly in machine building, conveyor technology, and plant engineering. It is employed wherever safe position detection is necessary, for example, with sliding doors, swing arms, lifting tables, or other movable components. The protection rating IP66 and IP67 makes it suitable for outdoor use or in damp, dust-laden environments, as it is dust- and waterproof. The ambient temperature range of -25 °C to +70 °C allows use in climatically demanding conditions.
Functions and Equipment in Detail
The switch features one normally closed contact (1 S) and one normally open contact (1 Ö), enabling it to be used both for signaling a state and for disconnecting electrical circuits. The safety function is achieved through forced opening according to IEC/EN 60947-5-1, meaning that the contacts are safely opened even in the event of mechanical failure or damage to the switch, preventing hazardous conditions. The housing cover is yellow, enabling visual identification. The housing is made of plastic, providing high mechanical stability with low weight.
Technology Explained Simply
Forced opening is a key safety feature: in the event of a mechanical defect, such as a broken plunger, the switching function is no longer controlled by mechanical movement but by a mechanical interlock that safely opens the contacts. This prevents the switch from remaining erroneously in a closed state, which must be avoided in safety-critical applications. Connections are made via screw terminals, ensuring a secure and durable electrical connection. The standard IEC/EN 60947 defines requirements for electrical safety and operational reliability of switches.
Compatibility and Accessories
The switch can be combined with various accessories to facilitate mounting or connection. These include, for example, M12 connectors and sockets (e.g. M12B, M12A, M12A5), enabling quick and secure connections. Additionally, screw caps (e.g. LS-X20), membrane screws (EMS20), and adapter plates (e.g. LS-XAP) are available, which can be used depending on mounting conditions and requirements. Guide washers (FS-AT) support correct guidance of the plunger.
Mounting and Installation
Mounting is carried out according to design EN 50047 form C, ensuring that the switches fit into standardized mounting holes. The screw terminals allow for simple and secure wiring. The protection rating IP66/IP67 requires no additional protective measures during installation, as the switch is already protected against dust and water. Mounting is typically done directly on the movable component or on the machine structure, with positioning such that the roller plunger is actuated during the desired movement.
Advantages in Operation
The LS-S11/P offers high reliability through the forced opening function, which ensures safety even in the event of mechanical failure. The robust plastic construction and protection rating IP66/IP67 make it resistant to environmental influences. The use of screw terminals enables simple and secure wiring. The yellow color of the housing cover supports visual identification during operation. Compliance with standard IEC/EN 60947 ensures electrical safety and compatibility with other components in the system.