| General |
| Protection function | Load isolation switch / main switch |
| Switching capacity SCCR 480Y/277 V 60 Hz | 100 kA |
| Switching capacity SCCR 600Y/347 V 60 Hz | 50 kA |
| Rated current In = Iu | 600 A |
| Number of poles | 3 way |
| Installation type | Built-in installation |
| Connection type | Screwed connection |
| Standard/approval | UL/CSA, IEC |
| Product type | Molded Case Switch |
The
power switch NS3-600-NA from
Eaton is a
3-pole switch disconnector designed for use in industrial and commercial electrical installations. It provides safe disconnection of electrical loads during operation and enables interruption of current flow during maintenance work or in the event of a fault. The switch is rated for a
nominal current of 600 A and offers high switching capacity, making it suitable for applications with high electrical loads. It complies with the standards
UL/CSA and
IEC, confirming adherence to international safety and quality standards.
Applications
The NS3-600-NA is designed for
fixed installation and is mounted in enclosures or distribution units where reliable and safe current disconnection is required. It is particularly suitable for installations in industry, machine building, manufacturing technology, as well as in building technology and energy distribution systems. The screw connection enables a robust and secure connection of conductors, designed for continuous operation.
Functions and Equipment in Detail
As a
switch disconnector, the NS3-600-NA serves as a main switch that disconnects the electrical load from the network. It is not designed for protection against overload or short circuit, but is intended solely for disconnection. The
switching capacities are specified for two voltage ranges: at 480Y/277 V and 60 Hz, the switching capacity (SCCR) is
100 kA (Icu), and at 600Y/347 V and 60 Hz, it is
50 kA (Icu). These values indicate the maximum current the switch can safely interrupt without damage. The
rated continuous current (In = Iu) is 600 A, indicating the maximum current the switch can carry continuously without overheating or failing.
Technology Explained Simply
The switch is a
Molded Case Switch, where the electrical components are housed in a plastic enclosure. This design provides high protection against external influences and simplifies installation. The
screw connection ensures a mechanically stable and electrically reliable connection. The switching function is operated via a mechanical lever that actuates the contact mechanism. The switching position is visible, which increases operational safety.
Compatibility and Accessories
The NS3-600-NA can be extended with various accessories to meet specific requirements. These include, for example,
undervoltage release units such as NZM2/3-XUHIV24AC or NZM2/3-XU600AC, which automatically disconnect the switch in case of voltage drop. For mechanical interlocking, options such as the
door coupling handle (e.g. NZM3-XTVD-0) or
remote control (NZM3-XR208-240AC) are available. Additionally,
finger protection covers (NZM3-XIPK) or
connection extensions (NZM3-XKV70) can be used for safe and flexible installation. The use of
CI enclosures (e.g. MCCB3-630/I48/I43E-200) enables integration into standardized enclosure constructions.
Installation and Mounting
Mounting is done in
fixed installation, where the switch is installed into a suitable enclosure or distribution unit. Connections are made via screw terminals, ensuring a secure connection. Installation requires compliance with applicable electrical standards and regulations. The switching position is visually identifiable, which facilitates operational monitoring.
Advantages in Operation
The NS3-600-NA offers high reliability and safety for current disconnection. The high switching capacity (Icu) enables use in installations with high short-circuit currents. Compliance with UL/CSA and IEC standards ensures international acceptance and usability. The modular expandability through accessories allows adaptation to specific requirements without impairing the basic function. The visible switching position increases operational safety and facilitates maintenance.