| Features |
| Circuit breaker type | Motor protective circuit breaker |
| Breaking capacity | 50000 A |
| Number of poles | 3 |
| International Protection (IP) code | IP20 |
| Pollution degree | 3 |
| Certification | IEC/EN 60947, VDE 0660 |
| Operational conditions |
| Operating temperature (T-T) | -25 - 55 °C |
| Storage temperature (T-T) | -40 - 80 °C |
| Power |
| Rated current | 16 A |
| Rated voltage | 690 V |
| Weight & dimensions |
| Width | 45 mm |
| Depth | 76 mm |
| Height | 93 mm |
The
motor protection circuit breaker from manufacturer Eaton, type PKM0-16 (manufacturer's number 044502), is a 3-pole short-circuit protection circuit breaker for use in industrial electrical installations. It provides protection against short circuits in electrical systems and is specifically designed for operation with motors, including motors of efficiency class IE3. The device is rated for a nominal operating voltage of 690 V and a rated current of 16 A, and features an instantaneous short-circuit tripping unit that trips at currents up to 248 A. The switching capacity is 50000 A, enabling high thermal and electrical load capacity.
Applications
This circuit breaker is designed for use in industrial installations, particularly in drive technology and for controlling electric motors. It is used in switchgear where secure protection against short circuits is required. The PKM0 size allows for compact mounting, especially in enclosures with limited space. Connection is made via screw terminals suitable for single- and multi-strand conductors with cross-sections from 1 to 6 mm². The stripping length is 10 mm, and the tightening torque for main conductors is 1.7 Nm.
Functions and Equipment in Detail
The switch features a fixed setting of the short-circuit tripping unit at 15.5 times the rated current (15.5 × Iu), with a tolerance of ±20 %. Temperature compensation is performed according to IEC/EN 60947 and VDE 0660 in the range of -5 °C to +40 °C, with residual error above 40 °C ≤ 0.25 %/K. The operating temperature ranges from -25 °C to +55 °C, while storage temperature ranges from -40 °C to +80 °C. The protection class IP20 ensures protection against contact with fingers and larger objects, but not against dust or water. The connection terminals are IP00, meaning they offer no additional protection.
Technology Explained Simply
The motor protection circuit breaker operates as a mechanical switching device that quickly and instantaneously disconnects the circuit in the event of a short circuit. The screw terminals ensure a secure and durable connection of conductors. The switching capacity of 50000 A demonstrates the device’s ability to handle high current surges without failure. The rated operating voltage of 690 V makes the switch suitable for high-voltage installations. The current heat losses amount to 6.43 W under 3-pole operating conditions, indicating efficient heat dissipation. The service life is mechanically 0.1 million switching operations and electrically (AC-3 at 400 V) also
0.1 million switching operations.
Compatibility and Accessories
The switch is designed for mounting on DIN rail according to IEC/EN 60715 with a height of 7.5 or 15 mm. It can also be clamped. Compatible accessories include various
under-voltage release units (e.g. U-PKZ0(380V50Hz), U-PKZ0(24VDC)),
auxiliary current release units (e.g. A-PKZ0 110 V 50 Hz),
busbar adapters (e.g. BBA0R-32),
DIN rail adapter plates (e.g. PKZM0-XC45L),
feed-in terminals (e.g. BK25/3-PKZ0-E),
support rails (e.g. PKZM0-XMR54),
contact blocks (e.g. PKZM0-XM32DE),
wiring blocks (e.g. PKZM0-XDM15ME),
normal auxiliary switches (e.g. NHI-E-11-PKZ0), and
insulating housing (e.g. E-PKZ0). These components extend the functionality of the switch, for example by integrating auxiliary switches or adapting to different switchgear configurations.
Mounting and Installation
Mounting is done either by snapping onto a DIN rail or by screw mounting. The cap mounting dimension is 45 mm, enabling standardization in enclosures. The installation orientation is arbitrary, although the power feed direction can be chosen as required. The maximum installation altitude is 2000 m above sea level, enabling use in high mountain regions. The connection cross-sections are designed for single-strand and fine-strand conductors with wire end ferrules according to DIN 46228.
Advantages in Operation
The circuit breaker provides reliable short-circuit protection with high switching capacity and is designed for use in demanding industrial environments. Compliance with standards IEC/EN 60947 and VDE 0660 ensures safe and standard-compliant operation. The combinability with various accessories allows flexible adaptation to different requirements. The touch protection according to VDE 0106 T. 100 protects during maintenance against electrical hazards. The high service life and low current heat losses contribute to operational safety and energy efficiency.