| Features |
| Circuit breaker type | Motor protective circuit breaker |
| Number of poles | 3 |
| International Protection (IP) code | IP20 |
| Pollution degree | 3 |
| Tripping method | Thermomagnetic |
| Product colour | Black, White |
| Certification | IEC/EN 60947, VDE 0660,UL, CSA |
| Operational conditions |
| Operating temperature (T-T) | -25 - 55 °C |
| Storage temperature (T-T) | -40 - 80 °C |
| Operating altitude | 0 - 2000 m |
| Power |
| Rated current | 10 A |
| Rated voltage | 690 V |
| Power dissipation | 6.48 W |
| Weight & dimensions |
| Width | 54 mm |
| Depth | 76 mm |
| Height | 93 mm |
The
motor protection circuit breaker from manufacturer Eaton, type PKZM0-10/NHI11, is a 3-pole circuit breaker for use in industrial electrical installations. It is specifically designed for the protection of electric motors and offers an integrated solution with pre-mounted
auxiliary contactor (1S1Ö), simplifying installation and commissioning. The pre-mounted configuration reduces unpacking and installation times, as no additional components need to be installed later. The circuit breaker is rated for a nominal current of 10 A and supports a nominal voltage of up to 690 V, making it suitable for a wide range of applications in industrial electrical engineering.
Applications
The motor protection circuit breaker is used in industrial plants where reliable protection for electric motors is required. It is particularly suitable for drives in machine building, conveyor technology, packaging technology, and other areas where motor protection plays a central role. The integrated configuration with auxiliary contactor allows direct use in control systems and switchgear without additional installation work. The operating temperature range of -25 to 55 °C and storage temperature range of -40 to 80 °C make it suitable for use in indoor environments and under moderate outdoor conditions. The maximum operating altitude is 2000 m above sea level, enabling use in mountainous regions or high-altitude locations.
Functions and Equipment in Detail
The circuit breaker operates using the
thermal-magnetic tripping method, combining both thermal and magnetic tripping functions. The thermal component protects against prolonged overloads, while the magnetic component reacts quickly to short-circuit currents. The nominal current range of 6.3 to 10 A allows flexible adaptation to various motor powers. The integrated
auxiliary contactor function (1S1Ö) enables signal integration into control systems, for example for status indication or remote control. The power loss is 6.48 W, which is relevant for operational safety and heat generation.
Technology Explained Simply
The
motor protection circuit breaker protects electric motors against overload and short circuit. The thermal tripping function responds to continuously elevated current values that could lead to motor overheating. The magnetic tripping function disconnects within milliseconds when sudden high currents occur, such as during short circuits. The IP20 protection rating means the circuit breaker is protected against contact with fingers and against solid foreign objects larger than 12.5 mm, but not against water or dust. The pollution degree rating of 3 indicates that the circuit breaker is designed for environments with light contamination, as commonly found in many industrial plants.
Compatibility and Accessories
The circuit breaker can be combined with various accessories to extend its functionality. These include, for example,
insulating housing (e.g. CI-K2-PKZ0-GR),
DIN rail adapters (e.g. PKZM0-XC45),
under-voltage release units (e.g. U-PKZ0(230V50HZ)-PI), and
load current release units (e.g. A-PKZ0 415 V 50 Hz). These components allow adaptation to specific requirements such as additional protection functions, mounting variants, or signal integration. The use of
dual adapters (e.g. Z-SS-60-ADD/6-54) or
busbar adapters (e.g. BBA0-25) enhances mounting flexibility. Certifications according to IEC/EN 60947, VDE 0660, UL, and CSA confirm compliance with international safety and quality standards.
Mounting and Installation
The circuit breaker is designed for mounting on standard DIN rail (DIN rail). Dimensions are 54 mm (width), 76 mm (depth), and 93 mm (height), allowing placement in standard switchgear enclosures. The pre-mounted configuration with auxiliary contactor reduces installation time, as no additional components need to be retrofitted. Mounting typically occurs in switchgear or control cabinets, with electrical connections to be made according to respective circuit diagrams and regulations. The operating altitude of up to 2000 m above sea level must be considered during planning, especially for installations in mountainous regions.
Operational Advantages
The use of the motor protection circuit breaker PKZM0-10/NHI11 provides reliable protection for electric motors. The integrated auxiliary contactor function enables direct integration into control systems, reducing system complexity. The thermal-magnetic tripping function ensures efficient protection against overload and short circuit. Certifications according to international standards (IEC/EN 60947, VDE 0660, UL, CSA) ensure quality and safety. The pre-mounted configuration shortens installation time and reduces error sources during commissioning. The operating temperature range of -25 to 55 °C and storage temperature range of -40 to 80 °C extend the range of possible applications in various environments.