Further information for Moeller 014479 Motor Protection Relay 1.6-2.4A 1S1Ö
Features
Product colour
Black, White
Certification
IEC/EN 60947, VDE 0660, UL, CSA
Overload protection
Operational conditions
Operating temperature (T-T)
-25 - 50 °C
Weight & dimensions
Weight
75 g
The Eaton motor protection relay ZE-2,4 is an overload relay for small contactors, used for motor protection functions in industrial applications. It is specifically designed for direct mounting on contactors from the DILEM, DIULEM/21/MV series and provides reliable protection against overloads. The device features integrated phase failure sensitivity in accordance with IEC/EN 60947 and VDE 0660 Part 102, enabling response to missing or unbalanced phase voltages. The operating temperature ranges from -25 °C to 50 °C, making it suitable for various industrial environments. The relay is available in black and white and complies with standards IEC/EN 60947, VDE 0660, UL, and CSA. The protection rating IP20 safeguards against contact with moving parts and ingress of solid foreign objects larger than 12.5 mm, but does not protect against water or dust.
Applications
The motor protection relay ZE-2,4 is used in systems where electric motors operate with rated currents between 1.6 A and 2.4 A. It is particularly suitable for applications in the manufacturing industry, packaging industry, or machine building, where continuous motor monitoring is required. Direct mounting on contactors enables compact integration into existing control systems without additional space requirements. Use with DILEM and DIULEM/21/MV series contactors ensures a compatible and standardized solution.
Functions and Equipment in Detail
The relay includes a Test/Off button, allowing manual verification of the protection function without operating the motor. The Reset button enables manual or automatic restart after tripping, with the option to switch between hand and auto reset. The free release ensures the contactor is immediately ready for operation again once the fault cause has been eliminated. The device is equipped with an auxiliary contact consisting of one normally open contact (1 S) and one normally closed contact (1 Ö), which can be used for additional control or signaling tasks.
Technology Explained Simply
The overload protection function of the ZE-2,4 is based on measuring the motor’s current consumption. If the current exceeds the set rated value (1.6–2.4 A), the contactor is switched off to protect the motor from thermal overload. The phase failure sensitivity detects when one or more phases of the supply voltage are missing or unbalanced, which can lead to uneven motor loading. The integrated auxiliary contacts allow connection to external control systems or warning systems, e.g., to trigger an alarm signal upon tripping. The IP20 protection rating means the device is protected against direct contact and ingress of large solid objects, but not against water or dust.
Compatibility and Accessories
The motor protection relay ZE-2,4 is specifically developed for use with contactors from the DILEM and DIULEM/21/MV series. It can be combined with various models of these series, including e.g. DILEEM-10(24V50Hz), DILEM-10(400V50Hz), DILEM12-01(230V50/60Hz), and DIULEEM/21/MV(230V50Hz 240V60Hz). Direct mounting on these contactors enables simple and secure installation. Compatibility with various voltage types (e.g. 24 V DC, 230 V AC, 400 V AC) and power ratings (3 kW to 5.5 kW) offers flexibility in selecting the appropriate contactor for the specific application.
Mounting and Installation
Mounting is done directly onto the contactor, with no additional fastening elements required. The connection terminals are designed for connection to the respective wires. The rated current range (1.6–2.4 A) is adjusted via a rotary control on the device. Operation of the buttons (Test/Off, Reset) is manual. Installation is carried out in a closed enclosure, as the IP20 protection rating does not provide protection against environmental moisture or dust.
Operational Advantages
The ZE-2,4 provides reliable and precise monitoring of motor current, extending motor lifespan. The integrated auxiliary contacts enable easy integration into existing control systems. Direct mounting on contactors reduces space requirements in the enclosure. The free release and the option to choose between hand and auto reset enhance operational safety and simplify maintenance. Certification according to IEC/EN 60947, VDE 0660, UL, and CSA ensures compliance with international safety and quality standards.