| General |
| Nominal voltage | 0,6/1 kV |
| Test voltage | 3 kV |
| Insulation resistance | 20 MΩ·km |
| Installation temperature range | -20 °C |
| Temperature range after installation | -40 °C |
| Maximum operating temperature | 90 °C |
| Minimum bending radius | 5 x cable diameter |
| Oil resistance | according to VDE 0472 T. 803, test type A |
| Flame retardancy | VDE 0482-332-1-2, IEC 60332-1 |
| Conductor marking | according to VDE 0293-308 |
| Conductor | tinned copper stranded wire, fine-stranded class 5 |
| Wire insulation | Rubber compound according to VDE 0207 T. 20 |
| Outer sheath | Rubber compound according to VDE 0207 T. 21 |
| Sheath colour | Yellow |
The NSSHÖU-J 4x1.5 from Draka Comteq is a heavy-duty rubber hose cable designed for applications with very high mechanical loads. It is particularly suitable for use in underground mining, open-pit mining, construction sites, and industrial environments. The cable is intended for use in dry and damp rooms as well as outdoors and can also be used for fixed installation, with specific operating conditions to be defined on a case-by-case basis. The sheath colour is yellow, which enables good visibility and identification.
Applications
The cable is designed for environments where high mechanical stresses, such as tension, pressure, bending, or abrasion, occur. Typical application scenarios include mobile equipment, conveying systems, construction machinery, or industrial production facilities, where high flexibility and durability of the cable are required. Outdoor use is possible due to the weather resistance of the outer sheath, with temperature limits ranging from -40 °C to +80 °C after installation.
Functions and Equipment in Detail
The cable consists of four conductors, each with a cross-section of 1.5 mm². Each conductor is insulated with a rubber compound according to VDE 0207 T. 20, ensuring high electrical insulation and mechanical strength. The conductors are stranded with optimal lay lengths to enable even distribution of mechanical stress and to increase flexibility. Conductor identification follows VDE 0293-308, allowing for clear identification of individual conductors. The conductors are made of fine-stranded, tinned copper wires of class 5, ensuring high flexibility and longevity under frequent bending.
Technology Explained Simply
The rated voltage is 0.6/1 kV, meaning the cable is designed for voltages up to 1 kV for alternating current and 0.6 kV for direct current. The test voltage of 3 kV serves as a safety check and ensures the insulation remains stable under increased voltage. The insulation resistance of 20 MΩ·km at 20 °C indicates the high electrical insulation properties of the cable. The maximum operating temperature is +90 °C, enabling high thermal load capacity. The minimum bending radius is 5 times the cable diameter for free installation, supporting flexibility during installation.
Compatibility and Accessories
The cable is designed for use in industrial and construction applications where high mechanical and thermal loads occur. It can be connected to standard terminals, plug connectors, or other electrical components rated for a nominal voltage of 0.6/1 kV. The use of protective conductors or additional protective measures is application-dependent and must be evaluated separately.
Installation and Mounting
The cable can be installed in dry and damp rooms as well as outdoors. During installation, a temperature of at least -20 °C is required; after installation, the cable can be operated at temperatures from -40 °C to +80 °C. The minimum bending radius is 5 times the cable diameter, which must be considered during installation to ensure the mechanical integrity of the cable. Installation is typically done exposed or in protective conduits, depending on environmental conditions.
Operational Advantages
The NSSHÖU-J 4x1.5 offers high mechanical strength and flexibility, making it suitable for mobile and stationary applications in demanding environments. The oil resistance according to VDE 0472 T. 803, test method A, protects the cable from mineral oil and other chemical substances. The flame retardancy according to VDE 0482-332-1-2 (IEC 60332-1) enhances safety in fire hazard situations. The fire behaviour according to VDE 0472 T. 804, test method B, meets the requirements for flame retardancy in electrical installations.
Protection Class and Environmental Conditions
The cable is designed for use in dry and damp rooms as well as outdoors. Temperature ranges are clearly defined: at least -20 °C during installation, up to -40 °C after installation. The maximum operating temperature is +90 °C, enabling high thermal load capacity. The cable is not specifically designed for use in explosive atmospheres, but this must be evaluated depending on the application and environment.
Material and Construction
The outer sheath is made of a rubber compound according to VDE 0207 T. 21, providing high mechanical strength, weather resistance, and oil resistance. The yellow colour of the sheath serves as visual identification and facilitates recognition during use. The copper wires are tinned and fine-stranded (class 5), ensuring high flexibility and longevity under frequent bending.