| General |
| SPD classification as per IEC 61643-41 | Type 1 + type 2 |
| Nominal voltage DC [L+ -- L-] (UN) | 1000 V |
| Nominal voltage DC [(L+/L-) -- PE] (UN) | 500 V |
| Max. continuous operating voltage (DC) [L+ -- L-] (UC) | 1000 V |
| Max. continuous operating voltage (DC) [(L+/L-) -- PE] (UC) | 500 V |
| Lightning impulse current (10/350 µs) (Iimp) | 5 kA |
| Nominal discharge current (8/20 µs) (In) | 12.5 kA |
| Max. nominal impulse discharge current (8/20 µs) (Imax) | 20 kA |
| Voltage protection level [DC+ -- DC-] (UP) | < 3,75 kV |
| Voltage protection level [(DC+/DC-) -- PE] (UP) | < 2,5 kV |
| Max. short circuit withstand capability (ISCCR) | 5 kA |
| Max. backup fuse | 80 A gG |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (min.) | 1.5 mm2 solid / flexible |
| Cross-sectional area (max.) | 35 mm2 stranded / 25 mm2 flexible |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP20 |
| Capacity | 4 Standard DIN module, DIN 43880 |
| Approvals | DEKRA, UL |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
| Extended technical data |
| For use in DC battery storage systems up to Ik | ≤ 100 kA |
| Backup fuse for DC battery storage systems up to IK | Bussman HLS 2,000 V DC / 200 A 2+/A173 DST aR, manuf. part no.: 170M2040 |
| No response up to 1,250 V DC [L+/L- -- PE] | |