General SPD classification as per EN 61643-11 / ... IEC 61643-11 type 2 / class II Energy coordination with terminal equipment (≤ 10 m) type 2 + type 3 Nominal voltage (d.c.) (UN) 500 V Max. continuous operating voltage DC (UC) 550 V Nominal discharge current (8/20 µs) (In) 12.5 kA Voltage protection level (UP) ≤ 2.0 kV Response time (tA) ≤ 25 ns Short-circuit withstand capability without backup fuse (d.c.) (ISCCR) 200 A Short-circuit withstand capability for max. mains-side overcurrent protection (d.c.) (ISCCR) 25 kA Max. mains-side overcurrent protection 35 A gG Temporary overvoltage (TOV) DC (UT) – characteristic 726 V / 5 sec. – withstand Temporary overvoltage (TOV) DC, 2x UC (UT) – characteristic 1100 V / 120 min. – safe failure Operating temperature range (TU) -40 °C ... +80 °C Operating state / fault indication green / red Number of ports 1 Cross-sectional area (min.) 1.5 mm2 solid / flexible Cross-sectional area (max.) 35 mm2 stranded / 25 mm2 flexible For mounting on 35 mm DINs rails acc. to EN 60715 Enclosure material thermoplastic, red, UL 94 V-0 Place of installation indoor installation Degree of protection IP20 Capacity 1.5 Standard DIN module, DIN 43880 Extended technical data DC and AC operation possible no
Einpoliger Überspannungsableiter DEHNguard SE DC, Typ 2 nach EN 61643-11, bestehend aus Basisteil und gestecktem Schutzmodul. Hohe Gerätesicherheit durch speziell für den Einsatz in DC-Stromkreisen geeignete leistungsfähige DC-Schaltvorrichtung DCD. Zum Schutz von Gleichstrom-Verbraucheranlagen vor Überspannungen. Zum Einsatz im Blitz-Schutzzonen-Konzept an den Schnittstellen 0B - 1 und höher.