| General |
| SPD as per EN 61673-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
| Energy coordination with terminal equipment (≤ 10 m) | Type 1 + type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 264 V (50 / 60 Hz) |
| Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal) | 75 kA |
| Specific energy [L1+L2+L3-PEN] (W/R) | 1.40 MJ/ohms |
| Lightning impulse current (10/350 µs) [L-PEN] (Iimp) | 25 kA |
| Specific energy [L-PEN] (W/R) | 156.25 kJ/ohms |
| Nominal discharge current (8/20 µs) [L-PEN] (In) | 25 kA |
| Voltage protection level (UP) | ≤ 1,5 kV |
| Open-circuit voltage of the combination wave generator (UOC) | 20 kV |
| Follow current extinguishing capability (a.c.) (Ifi) | 50 kArms |
| Integrated overcurrent protection | Yes, ACI technology |
| Integrated ACI technology is selective to upstream fuse | ≥ 100 A gG |
| Short-circuit withstand capability (ISCCR) | 50 kArms |
| Response time (tA) | ≤ 100 ns |
| Temporary overvoltage (UT) – characteristic | 440 V / 120 min. – withstand |
| Operating temperature range (TU) | -40°C to +80°C |
| Operating state / fault indication | Green / red (inspection window) |
| Module disconnection indication | Green (side view) |
| Number of ports | 1 |
| Cross-sectional area (L1, L2, L3, PEN, ) (min.) | 6 mm² solid / fine-stranded |
| Cross-sectional area (L1, L2, L3, PEN, ) (max.) | 35 mm² stranded / 25 mm² fine-stranded |
| For mounting on | 35-mm DIN rail as per EN 60715 / busbar |
| Place of installation | Indoor |
| Degree of protection | IP 20 |
| Capacity | 11 Standard DIN module, DIN 43880 |
| When used in switchgear with prospective short-circuit currents exceeding 50 kArms (tested by VDE) |
| Max. prospective short-circuit current | 100 kAeff (220 kApeak) |
| Limitation / Extinction of mains follow currents | up to 100 kArms (220 kApeak) |