| General |
| SPD according to EN 61643-11 / IEC 61643-11 | type 1 / class I |
| Max. continuous operating voltage (AC) (UC) | 440 V (50 / 60 Hz) |
| Lightning impulse current (10/350 µs) (Iimp) | 100 kA |
| Voltage protection level (UP) | ≤ 2.5 kV |
| Approvals | UL |
Single-pole, coordinated N-PE lightning current arrester DEHNgap Maxi, type 1 according to EN 61643-11. Total current arrester specially for use in the TT system in the 3+1 and 1+1 circuit according to DIN VDE 0100-534 between N and PE for Uc = 440V. For protecting low-voltage consumer systems against overvoltages, even in the event of direct lightning strikes. For use in the lightning protection zone concept at the interfaces 0A - 1 in the 3+1 circuit variant.