| General |
| SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
| Energy coordination with terminal equipment (≤ 10 m) | Type 1 + type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 800 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 880 V (50 / 60 Hz) |
| Lightning impulse current (10/350 µs) [1,2-3] (Iimp) | 12.5 kA |
| Specific energy [1,2-3] (W/R) | 39.06 kJ/Ohm |
| Nominal discharge current (8/20 µs) [1,2-3] (In) | 20 kA |
| Voltage protection level [1,2-3] (UP) | ≤ 4 kV |
| Follow current limitation / Selectivity | No tripping of a 35 A gG fuse up to 50 kArms (prosp.) |
| Short-circuit withstand capability [1,2-3] (ISCCR) | 25 kArms |
| Response time (tA) | ≤ 100 ns |
| Max. backup fuse (L) up to IK = 50 kArms | 160 A gG |
| Operating temperature range (parallel connection) (TUP) | -40°C to +80°C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area [1,2,3] (min.) | 6 mm2 solid / fine-stranded |
| Cross-sectional area [1,2,3] (max.) | 35 mm2 stranded / 25 mm2 fine-stranded |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Place of installation | Indoor |
| Degree of protection | IP 20 |
| Capacity | 8 Standard DIN module, DIN 43880 |
| Type of remote signalling contact | yes / changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / fine-stranded |
| Supplementary data |
| Anti-PID voltage (U1-3 + UPID) | 508 VAC + 750 VDC – withstand |
| Max. prospective short-circuit current | 50 kArms |
Mehrpolige Blitz- und Überspannungsableiteranordnung DEHNventil modular, Typ 1 + Typ 2 nach EN 61643-11 auf Funkenstreckenbasis, bestehend aus aus drei DEHNventil DV M2 440 SN 1891 FM und einem DEHNventil DV M2 W 440 SN 1893 FM. Höchste Anlagenverfügbarkeit durch Rapid Arc Control (RAC) Funkenstrecken. Zum Schutz von 800 V AC Photovoltaik-Systemen vor Überspannungen, auch bei direkten Blitzeinschlägen. Einsetzbar nach dem Blitz-Schutzzonen-Konzept an den Schnittstellen 0A - 1.