DEHN 961120, EAN: 4013364118614

DEHN 961120 DB M 1 255 surge arrester Type 1

Installation > Grounding Systems > Lightning protection material

DEHN 961120 DB M 1 255 surge arrester Type 1

Lieske Part No. 712913
Mfg Part No 961120
EAN-Code 4013364118614
Manufacturer DEHN
Here only 368,22 EUR
438,18 EUR incl. VAT

Further information for DEHN 961120 DB M 1 255 surge arrester Type 1

Extended technical data
Max. prospective short-circuit current100 kArms (220 kApeak)
Limitation / Extinction of mains follow currentsup to 100 kArms (220 kApeak)
Max. backup fuse (L) up to IK = 100 kArms (ta ≤ 0.2 s)500 A gG
Max. backup fuse (L) up to IK = 100 kArms (ta ≤ 5 s)315 A gG
Supplementary data
Nominal discharge current (8/20 µs) (In)50 kA
Technical data
SPD according to EN 61643-11 / IEC 61643-11type 1 / class I
Nominal voltage (a.c.) (UN)230 V (50 / 60 Hz)
Max. continuous operating voltage (AC) (UC)255 V (50 / 60 Hz)
Lightning impulse current (10/350 µs) (Iimp)50 kA
Specific energy (W/R)625.00 kJ/ohms
Voltage protection level (UP)≤ 2.5 kV
Follow current extinguishing capability (a.c.) (Ifi)50 kArms
Follow current limitation / Selectivityno tripping of a 32 A gG fuse up to 50 kArms (prosp.)
Response time (tA)≤ 100 ns
Max. backup fuse (L) up to IK = 50 kArms (ta ≤ 0.2 s)500 A gG
Max. backup fuse (L) up to IK = 50 kAeff (ta ≤ 5 s)315 A gG
Max. backup fuse (L-L')125 A gG
Temporary overvoltage (UT) – characteristic440 V / 120 min. – withstand
Operating temperature range (parallel connection) (TUP)-40 °C ... +80 °C
Operating temperature range (through-wiring) (TUS)-40 °C ... +60 °C
Operating state / fault indicationgreen / red
Number of ports1
Cross-sectional area (L/N, L'/N', N/PE(N)) (min.)10 mm2 solid / flexible
Cross-sectional area (L/N, N/PE(N)) (max.)50 mm2 stranded / 35 mm2 flexible
Cross-sectional area (L'/N') (max.)35 mm2 stranded / 25 mm2 flexible
For mounting on35 mm DIN rails acc. to EN 60715
Enclosure materialthermoplastic, red, UL 94 V-0
Place of installationindoor installation
Degree of protectionIP 20
Capacity2 Standard DIN module, DIN 43880
ApprovalsVDE, KEMA, UL
Test values according to UL 1449
SPD classification according to UL 1449Component (Type 4) SPD for SPD Type 2 application
Rated A.C. Voltage230 V
Frequency60 Hz
Max. Continuous Operating Voltage (AC) [L-N] (MCOV)255 V
Voltage Protection Rating [L-N] (VPR)1500 V
Amperage (series connection)115 A
Nominal discharge current (8/20µs) ( In)20 kA
Operating Temperature Range-40°C…+85°C
Cross-sectional area (L/N, L'/N', N/PE(N))AWG 8 Cu stranded
Torque (L/N, L'/N', N/PE(N))65 ポンドインチ
Single-pole, coordinated DEHNbloc modular lightning current arrester, type 1 according to EN 61643-11 on a spark gap basis, consisting of a base part and a plugged-in protection module. Maximum system availability thanks to RADAX-Flow follow current limitation. For protecting low-voltage consumer systems against overvoltages, even in the event of direct lightning strikes. For use in the lightning protection zone concept at the interfaces 0A - 1.