| Standards |
| Certification | UL |
| UL Standard | UL 1449 5th edition |
| UL File Number | E319777 |
| Technical data |
| SPD according to EN 61643-11 / IEC 61643-11 | type 1 / class I |
| Nominal voltage (a.c.) (UN) | 120 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 150 V (50 / 60 Hz) |
| Lightning impulse current (10/350 µs) (Iimp) | 35 kA |
| Specific energy (W/R) | 306.25 kJ/ohms |
| Voltage protection level (UP) | ≤ 1.5 kV |
| Follow current extinguishing capability (a.c.) (Ifi) | 35 kArms |
| Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 35 kArms (prosp.) |
| Response time (tA) | ≤ 100 ns |
| Max. backup fuse (L) up to IK = 35 kArms (ta ≤ 0.2 s) | 500 A gG |
| Max. backup fuse (L) up to IK = 35 kArms (ta ≤ 5 s) | 315 A gG |
| Max. backup fuse (L) for IK 35 kArms | 200 A gG |
| Max. backup fuse (L-L') | 125 A gG |
| Temporary overvoltage (UT) – characteristic | 230 V / 120 min. – withstand |
| Operating temperature range (parallel connection) (TUP) | -40 °C ... +80 °C |
| Operating temperature range (through-wiring) (TUS) | -40 °C ... +60 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (L/N, L'/N', N/PE(N)) (min.) | 10 mm2 solid / flexible |
| Cross-sectional area (L/N, N/PE(N)) (max.) | 50 mm2 stranded / 35 mm2 flexible |
| Cross-sectional area (L'/N') (max.) | 35 mm2 stranded / 25 mm2 flexible |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 20 |
| Capacity | 2 Standard DIN module, DIN 43880 |
| Approvals | UL, CSA |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
| Test values according to UL 1449 |
| SPD classification according to UL 1449 | Component (Type 4) SPD for SPD Type 2 application |
| Rated A.C. Voltage | 120 V |
| Frequency | 60 Hz |
| Max. Continuous Operating Voltage (AC) [L-N] (MCOV) | 150 V |
| Voltage Protection Rating [L-N] (VPR) | 1500 V |
| Amperage (series connection) | 115 A |
| Nominal discharge current (8/20µs) ( In) | 20 kA |
| Operating Temperature Range | -40°C…+85°C |
| Cross-sectional area (L/N, L'/N', N/PE(N)) | AWG 8 Cu stranded |
| Torque (L/N, L'/N', N/PE(N)) | 65 ポンドインチ |
| Connection of remote signalling contact | Class 2 circuits only |
| Cross-sectional area (remote indicator) | AWG 14-22 |
| Torque (remote indicator) | 3 Lbs-in |
Single-pole, coordinated DEHNbloc modular lightning current arrester, type 1 according to EN 61643-11 on a spark gap basis, consisting of a base part and a plugged-in protection module. Maximum system availability thanks to RADAX-Flow follow current limitation. For protecting low-voltage consumer systems against overvoltages, even in the event of direct lightning strikes. For use in the lightning protection zone concept at the interfaces 0A - 1.