| General |
| Energy coordination with terminal equipment (≤ 10 m) | type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 690 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 1000 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 15 kA |
| Max. discharge current (8/20 µs) (Imax) | 40 kA |
| Voltage protection level (UP) | ≤ 5 kV |
| Response time (tA) | ≤ 25 ns |
| Max. mains-side overcurrent protection | 100 A gG |
| Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR) | 25 kArms |
| Temporary overvoltage (UT) – characteristic | 1550 V / 5 sec. – withstand, 1320 V / 120 min. – withstand |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (min.) | 1.5 mm2 solid / flexible |
| Cross-sectional area (max.) | 35 mm2 stranded / 25 mm2 flexible |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 20 (integrated) |
| Capacity | 1.5 Standard DIN module, DIN 43880 |
| Approvals | UL |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
| Supplementary data |
| Sparkover voltage gas discharge tube (Uagmin) | 2200 V |
Single-pole surge arrester DEHNguard SE H, consisting of a base part and plugged-in protection modules. High discharge capacity due to powerful zinc oxide varistors. For protecting low-voltage consumer systems against surges. For use in the lightning protection zone concept at the interfaces 0B - 1 and higher.