| General |
| Degree of protection | Type 2 |
| Norm | EN 61643-11 |
| System type | TN-C |
| Monitoring technology | Thermo-Dynamik-Control |
| Application | Lightning protection zone concept at interfaces 0B - 1 and higher |
| Type of device | Multipole surge arrester |
| Manufacturer | DEHN |
| Model designation | DG M TNC 275 |
| Arrester use at 16.7 Hz – traction power supply systems |
| Test voltage AC (UC) | 275 V |
| Nominal AC voltage (UN) | 230 / 400 V |
| Nominal frequency AC (fN) | 16.7 Hz |
| Technical data |
| Energy coordination with terminal equipment (≤ 10 m) | type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 275 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 20 kA |
| Max. discharge current (8/20 µs) (Imax) | 40 kA |
| Voltage protection level (UP) | ≤ 1.5 kV |
| Voltage protection level at 5 kA (UP) | ≤ 1 kV |
| Response time (tA) | ≤ 25 ns |
| Max. mains-side overcurrent protection | 125 A gG |
| Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR) | 50 kArms |
| Temporary overvoltage (UT) – characteristic | 335 V / 5 sec. – Festigkeit, 440 V / 120 min. – sicherer Ausfall |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (min.) | 1.5 mm2 solid / flexible |
| Cross-sectional area (max.) | 35 mm2 stranded / 25 mm2 flexible |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 20 (integrated) |
| Capacity | 3 Standard DIN module, DIN 43880 |
| Approvals | DEKRA, VDE, UL |
The DEHNguard M TNC 275 is a multipole surge arrester of Type 2 category, designed for the protection of low-voltage consumer installations against transient overvoltages. The manufacturer is DEHN, and the device carries the manufacturer's number 952300. It is used within the lightning protection zone concept, particularly at interfaces 0B – 1 and higher, where the risk of overvoltages due to direct or indirect lightning strikes as well as electrical disturbances in the network is particularly high. The device consists of a base unit and plug-in protection modules, which can be modularly adapted to match the respective installation configuration.
Applications
This surge arrester is specifically designed for TN-C systems, in which the protective earth (PE) and neutral conductor (N) functions are combined. It protects electrical consumer installations in buildings, industrial facilities, and other installations where high availability and device safety are required. The application typically occurs in the field of distribution technology, where energy supply is distributed over multiple phases and a common conductor. Installation takes place at the interface between the external installation and the interior space to protect the energy supply against transient voltage spikes.
Functions and Equipment in Detail
The device offers high device safety through integrated arrester monitoring with Thermo-Dynamic-Control. This technology continuously monitors the condition of the arrester and responds to thermal changes that may indicate damage or overload. This enables early detection of defects, thereby increasing operational safety. The protection modules are plug-in and can be exchanged or supplemented according to requirements, allowing flexible adaptation to different system configurations.
Technology Explained Simply
The DEHNguard M TNC 275 operates according to the standards of EN 61643-11, which apply to surge protection devices of Type 2 category. This standard defines the requirements for electrical and mechanical properties as well as testing procedures. The arrester rapidly switches to the conductor and grounding path during overvoltages to divert voltage spikes and protect connected devices. The Thermo-Dynamic-Control technology monitors thermal conditions within the arrester to ensure it is not overloaded during operation. This is particularly important in systems with high load and frequent overvoltage events.
Compatibility and Accessories
The device is designed for TN-C systems, in which neutral and protective earth conductors are combined. It is therefore not suitable for TN-S or TT systems, where the conductors are separated. The modular design allows combination with additional protection modules, provided these are recommended by the manufacturer for the same assembly group. Exact compatibility with other modules must be verified in the manufacturer’s technical documentation.
Mounting and Installation
Mounting is typically performed in distribution boxes or enclosures, where the energy supply is connected to the consumer installation. Installation requires compliance with VDE and EN standards, as well as correct connection of the conductors (L1, L2, L3, N/PE) to the respective terminal clamps. The protection modules are plugged into the base unit, with correct polarity and the appropriate number of modules depending on the system configuration to be observed. The cross-sections of the connections must comply with the requirements of the respective standards.
Advantages in Operation
The DEHNguard M TNC 275 provides reliable protection for electrical installations in TN-C systems. The integrated monitoring technology increases operational safety, as defects can be detected early. The modular design allows flexible adaptation to different installation configurations without requiring the entire device to be replaced. Compliance with the EN 61643-11 standard ensures standardized quality and performance, recognized in industry and building management. Use within the lightning protection zone concept at interfaces 0B – 1 and higher ensures the installation is protected against the most common overvoltage sources.