| Technical data |
| Max. continuous operating voltage (AC) (UC) | 440 |
| Nominal discharge current (8/20 µs) (In) | 20 kA |
| Max. discharge current (8/20 µs) (Imax) | 40 kA |
| Voltage protection level (UP) | ≤ 2 kV |
| Max. mains-side overcurrent protection | 125 A gG |
| Approvals | DEKRA, VDE, UL, VdS, CSA |
| Type of remote signalling contact | changeover contact |
| Test values according to UL 1449 |
| Rated Voltage (AC, 50/60 Hz) | 440 V |
| MCOV (AC, 50/60 Hz) | 440 V |
| Nominal discharge current (8/20µs) ( In) | 20 kA |
| Maximum ambient temperature | 85 °C |
| UL 1449 edition | 5th edition |
| Type (SPD classification) | Type 4 component assembly |
Single-pole surge arrester DEHNguard S, type 2 according to EN 61643-11, consisting of a base part and a plugged-in protection module. High device safety due to arrester monitoring with thermo-dynamic control. For protecting low-voltage consumer systems against surges. For use in the lightning protection zone concept at the interfaces 0B - 1 and higher.