| General |
| SPD according to EN 61643-11 / IEC 61643-11 | type 2 / class II |
| Max. continuous operating voltage (AC) (UC) | 1000 V (50 / 60 Hz) |
| Max. discharge current (8/20 µs) (Imax) | 30 kA |
| Voltage protection level (Up) | ≤ 4.2 kV |
| Max. overcurrent protection | 100 A aM |
| Max. overcurrent protection at U ≤ 690 V a.c. | 125 A gG |
| Approvals | UL |
Single-pole, compact surge arrester DEHNguard 1000, type 2 according to EN 61643-11 with rated voltage Uc = 1000V AC. High monitoring reliability due to disconnection device with thermo-dynamic control. For protecting low-voltage consumer systems against surges. For use in the lightning protection zone concept at the interfaces 0B - 1 and higher.