| Technical data |
| Energy coordination with terminal equipment (≤ 10 m) | type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 385 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 20 kA |
| Max. discharge current (8/20 µs) (Imax) | 40 kA |
| Nominal load current for “V-connection” (IL) | 40 A |
| Voltage protection level (UP) | ≤ 1.75 kV |
| Voltage protection level at 5 kA (UP) | ≤ 1.35 kV |
| Response time (tA) | ≤ 25 ns |
| Max. mains-side overcurrent protection | 125 A gG |
| Max. mains-side overcurrent protection with “V-connection” | 40 A gG |
| Max. mains-side overcurrent protection with stub wiring (double connection 2 x 10 mm²) | 125 A gG |
| Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR) | 25 kArms |
| Temporary overvoltage (UT) – characteristic | 335 V / 5 sec. – Festigkeit, 440 V / 120 min. – Festigkeit |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (min.) | 1,5 mm2 eindrähtig, 6 mm2 feindrähtig |
| Cross-sectional area (max.) | 10 mm2 solid / fine stranded |
| Cross-sectional area (min.) with wire end ferrule | 1.5 mm² |
| Cross-sectional area (max.) with wire end ferrule | 6 mm² |
| Cross-sectional area (max.) with wire end ferrule without collar | 10 mm² |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 20 |
| Capacity | 3 Standard DIN module, DIN 43880 |
| Approvals | DEKRA, VDE |
| Type of remote signalling contact | changeover contact |
| Switching capacity (a.c.) | 250 V / 0.5 A |
| Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
| Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Mehrpoliger Überspannungsableiter DEHNguard MP, Typ 2 + Typ 3 nach EN 61643-11, bestehend aus Basisteil mit gesteckten Schutzmodulen und Doppel-Push-In-Anschlussklemme für Stich- und Durchgangsverdrahtung geeignet. Hohe Gerätesicherheit durch Ableiterüberwachung mit Thermo-Dynamik-Control. Zum Schutz von Niederspannungs-Verbraucheranlagen vor Überspannungen. Zum Einsatz im Blitz-Schutzzonen-Konzept an den Schnittstellen 0B - 1 und höher.