| General |
| SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
| Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 255 V (50 / 60 Hz) |
| Lightning impulse current (10/350 µs) [L+N-PE] (Itotal) | 25 kA |
| Specific energy [L+N-PE] (W/R) | 156.25 kJ/Ohm |
| Lightning impulse current (10/350) [L-N]/[N-PE] (Iimp) | 12.5 / 25 kA |
| Specific energy [L-N]/[N-PE] (W/R) | 39.06 / 156.25 kJ/Ohm |
| Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In) | 12.5 / 25 kA |
| Voltage protection level [L-N]/[N-PE] (UP) | ≤ 1.5 / ≤ 1.5 kV |
| Follow current extinguishing capability [L-N]/[N-PE] (Ifi) | 25 kArms / 100 Arms |
| Follow current limitation / Selectivity | no tripping of a 32 A gG fuse up to 25 kArms (prosp.) |
| Response time (tA) | ≤ 100 ns |
| Max. mains-side overcurrent protection | 160 A gG |
| Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
| Temporary overvoltage (TOV) [N-PE] (UT) - Characteristic | 1200 V / 200 ms – withstand |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (L, N, PE, ) (min.) | 1.5 mm2 solid / flexible |
| Cross-sectional area (L, N, PE, ) (max.) | 35 mm2 stranded / 25 mm2 flexible |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 20 |
| Capacity | 2 Standard DIN module, DIN 43880 |
| Approvals | KEMA, VDE, UL |
| Extended technical data |
| Voltage protection level [L-PE] (UP) | 2.0 kV |
Multipole, application-optimized DEHNshield combined surge arrester, type 1 + type 2 according to EN 61643-11 based on spark gaps. Space-saving spark gap technology with only 1 module per pole enables compact design. For the protection of residential buildings and for use in special applications. Enables terminal equipment protection. For protection against overvoltages, even in the event of direct lightning strikes. Can be used according to the lightning protection zone concept at the interfaces 0A - 2.