| Extended technical data |
| Max. discharge current (8/20 µs) [1/2 - PG], [1+2 - PG] (Imax) | 20 kA |
| Technical data |
| SPD class | W |
| Impulse category | C1, C3 |
| Nominal voltage (UN) | 12 V |
| Max. continuous operating voltage DC (UC) | 15 V |
| Max. continuous operating a.c. voltage (UC) | 10.6 V |
| Nominal current at 60 °C (IL) | 10 A |
| Nominal current at 80°C (IL) | 6 A |
| C1 Total nominal discharge current (8/20 µs) (In) | 3 kA |
| C1 Nominal discharge current (8/20 µs) per line (In) | 1.5 kA |
| Voltage protection level line-line for In C1 (UP) | ≤ 80 V |
| Voltage protection level line-PG for In C1 (UP) | ≤ 50 V |
| Voltage protection level line-line at 1 kV/µs C3 (UP) | ≤ 44 V |
| Voltage protection level line-PG at 1 kV/µs C3 (Up) | ≤ 22 V |
| Series resistance per line | 0 Ohm |
| Cut-off frequency line-PG at 100 ohms (fG) | 0.6 MHz |
| Capacitance line-line (C) | ≤ 3 nF |
| Capacitance line-PG (C) | ≤ 6 nF |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Degree of protection | IP 20 |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Connection (input / output) | push-in / push-in |
| Cross-sectional area, solid | 0.2-2.5 mm2 |
| Cross-sectional area, flexible | 0.2-2.5 mm2 |
| Earthing via | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | polyamide PA 6.6 |
| Colour | yellow |
| Test standards | IEC 61643-21 / EN 61643-21 |
| Approvals | UL 497B, SIL |
| SIL classification | up to SIL3 *) |
| Test values according to UL 497b |
| Type (SPD classification) | BCO CL2 E 12 |
| Strike voltage Line to Ground 100 V/s min. | 33,4 V |
| Strike voltage Line to Ground 100 V/s max. | 37 V |
| Strike voltage Line to Line 100 V/s min. | 16,7 V |
| Strike voltage Line to Line 100 V/s max. | 18,5 V |