| Technical data |
| SPD class | L |
| Impulse category | D1, C1, C2, C3, B2 |
| Nominal voltage (UN) | 24 V |
| Max. continuous operating voltage DC (UC) | 36 V |
| Max. continuous operating a.c. voltage (UC) | 25.4 V |
| Nominal current at 80°C (IL) | 3 A |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 5 kA |
| D1 Lightning impulse current (10/350 µs) per line (Iimp) | 2.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 20 kA |
| C2 Nominal discharge current (8/20 µs) per line (In) | 10 kA |
| Voltage protection level line-PG for In C2 (UP) | ≤ 650 V |
| Voltage protection level line-line at 1 kV/µs C3 (UP) | ≤ 55 V |
| Voltage protection level line-PG at 1 kV/µs C3 (Up) | ≤ 600 V |
| Series resistance per line | 0 Ohm |
| Cut-off frequency line-line at 100 ohms (fG) | 1.5 MHz |
| Capacitance line-line (C) | ≤ 3 nF |
| Capacitance line-PG (C) | ≤ 42 pF |
| Operating temperature range (TU) | -40°C to +80°C |
| Operating state / fault indication | green / red |
| Degree of protection | IP 20 |
| Connection (input / output) | Push-in / Push-in |
| Cross-sectional area, solid | 0.2-2.5 mm2 |
| Cross-sectional area, flexible | 0.2-2.5 mm2 |
| Earthing via | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | Polyamide PA 6.6, UL 94 V-0 |
| Colour | yellow |
| Test standards | IEC 61643-21 / EN 61643-21 |
| Approvals | UL 497B, SIL |
| SIL classification | up to SIL3 *) |
Platzsparender, kompakter Kombi-Ableiter in 12 mm Baubreite und Push-In Anschlusstechnik mit Statusanzeige zum Schutz von erdfreien 4-Leiter-Messkreisen für informationstechnische Systeme und MSR-Technik.