| Technical data |
| SPD class | V |
| Impulse category | C1, C2, C3 |
| Nominal voltage (UN) | 230 V |
| Nominal current at 80°C (IL) | 3 A |
| C2 Total nominal discharge current (8/20 µs) (In) | 6 kA |
| C2 Nominal discharge current (8/20 µs) per line (In) | 3 kA |
| Voltage protection level line-PG for In C2 (UP) | ≤ 1100 V |
| Voltage protection level line-PG at 1 kV/µs C3 (Up) | ≤ 1100 V |
| Series resistance per line | 0 Ohm |
| Cut-off frequency line-PG at 100 ohms (fG) | 200 MHz |
| Capacitance line-line (C) | ≤ 7.32 pF |
| Capacitance line-PG (C) | ≤ 12 pF |
| Operating temperature range (TU) | -40°C to +80°C |
| Operating state / fault indication | green / red |
| Degree of protection | IP 20 |
| Connection (input / output) | Push-in / Push-in |
| Cross-sectional area, solid | 0.2-2.5 mm2 |
| Cross-sectional area, flexible | 0.2-2.5 mm2 |
| Earthing via | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | Polyamide PA 6.6 |
| Colour | yellow |
| Test standards | IEC 61643-21 / EN 61643-21 |
| Approvals | SIL |
| SIL classification | up to SIL3 *) |
Platzsparender, modularer Überspannungs-Ableiter in 6 mm Baubreite und Push-In Anschlusstechnik mit Statusanzeige zum Schutz von 2 Adern mehradriger, erdpotentialfreier Signalschnittstellen mit Nennspannung 230 V AC. Mit Signaltrennung für Wartungszwecke. Erfüllt u. a. die Anforderungen für signaltechnische Anlagen in der Bahnindustrie (DB RIL 819.0808 konform).