| Extended technical data |
| Max. discharge current (8/20 µs) [1/2 - PG], [1+2 - PG] (Imax) | 20 kA |
| Discharge current (8/20 µs) [1/2 - PG], [1+2 - PG] | 10 kA (10x) |
| Voltage protection level line-PG at 1 kV/μs C3 after being subjected to Imax (UP) | ≤ 600 V |
| Standards |
| Certification | UL |
| UL Standard | UL 497b |
| UL File Number | E156818 |
| Technical data |
| SPD class | L |
| Impulse category | D1, C1, C2, C3, B2 |
| Nominal voltage (UN) | 48 V |
| Max. continuous operating voltage DC (UC) | 56 V |
| Max. continuous operating a.c. voltage (UC) | 39.6 V |
| Nominal current at 70 °C (IL) | 0.75 A |
| D1 Total lightning impulse current (10/350 µs) (Iimp) | 3 kA |
| D1 Lightning impulse current (10/350 µs) per line (Iimp) | 1.5 kA |
| C2 Total nominal discharge current (8/20 µs) (In) | 10 kA |
| C2 Nominal discharge current (8/20 µs) per line (In) | 5 kA |
| Voltage protection level line-line for In C2 (UP) | ≤ 90 V |
| Voltage protection level line-PG for In C2 (UP) | ≤ 600 V |
| Voltage protection level line-line for In C1 (UP) | ≤ 90 V |
| Voltage protection level line-PG for In C1 (UP) | ≤ 600 V |
| Voltage protection level line-line at 1 kV/µs C3 (UP) | ≤ 70 V |
| Voltage protection level line-PG at 1 kV/µs C3 (Up) | ≤ 600 V |
| Series resistance per line | 1 Ohm |
| Cut-off frequency line-line (fG) | 7.2 MHz |
| Capacitance line-line (C) | ≤ 1 nF |
| Capacitance line-PG (C) | ≤ 16 pF |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Degree of protection | IP 20 |
| Connection (input / output) | push-in / push-in |
| Cross-sectional area, solid | 0.2-2.5 mm2 |
| Cross-sectional area, flexible | 0.2-2.5 mm2 |
| Earthing via | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | polyamide PA 6.6 |
| Colour | yellow |
| Test standards | IEC 61643-21 / EN 61643-21 |
| Approvals | UL 497B, CSA, ATEX, IECEx, CCC, SIL |
| SIL classification | up to SIL3 *) |
| ATEX approvals | TÜV 20 ATEX 8527 X: II 3G Ex ec IIC T4 Gc |
| IECEx approvals | IECEx TUR 20.0063X: Ex ec IIC T4 Gc |
| China Compulsory Certification | CCC no. 2021312304001192 |
| Test values according to UL 497b |
| Type (SPD classification) | BCO ML2 BD 48 |
| Strike voltage Line to Ground 100 V/s min. | 62,2 V |
| Strike voltage Line to Ground 100 V/s max. | 68,8 V |
| Strike voltage Line to Line 100 V/s min. | 72 V |
| Strike voltage Line to Line 100 V/s max. | 108 V |
Space-saving, modular combined surge arrester with a width of 6 mm and push-in connection technology with status display for protecting 1 double wire of floating symmetrical interfaces. With signal separation for maintenance purposes.