| General |
| SPD according to EN 61643-11 / IEC 61643-11 | type 3 / class III |
| Nominal voltage (a.c.) (UN) | 230 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 255 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 3 kA |
| Total discharge current (8/20 µs) [L+N-PE] (Itotal) | 5 kA |
| Combination wave (UOC) | 6 kV |
| Combination wave [L+N-PE] (UOC total) | 10 kV |
| Voltage protection level [L-N] / [L/N-PE] (UP) | ≤ 1250 / ≤ 1500 V |
| Response time [L-N] (tA) | ≤ 25 ns |
| Response time [L/N-PE] (tA) | ≤ 100 ns |
| Max. mains-side overcurrent protection | B 16 A |
| Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR) | 1 kArms |
| Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 335 V / 5 sec. – withstand, 440 V / 120 min. – safe failure |
| Temporary overvoltage (TOV) [L/N-PE] (UT) – Characteristic | 335 V / 120 min. – withstand, 440 V / 5 sec. – withstand |
| Temporary overvoltage (TOV) [L+N-PE] (UT) – Characteristic | 1200 V + UREF / 200 ms – safe failure |
| Operating temperature range (TU) | -25 °C ... +40 °C |
| Fault indication | acoustic signal on |
| Number of ports | 1 |
| Connecting wires | 1 mm2, 120 mm long |
| For mounting on | standard earthed socket outlets |
| Enclosure material | thermoplastic, red, UL 94 V-2 |
| Place of installation | indoor installation |
| Degree of protection of installed device | IP 20 |
| Dimensions | 54 x 54 x 32 mm |
Dehn surge protective device ÜS module STC for installation behind standard power outlets. Arresters of requirement class D according to E DIN VDE 675-6:
989 - Two-pole surge protection with control and Abtrennvorrichtg. -Acoustic fault indication (no power cut-off) with test func. Arrester rated voltage: 255 V / 5 Hz Nominal discharge current (8/29): 2.5 kA Type: 92435 Quantity: