| General |
| Degree of protection | IP 20 |
| Protection circuitry | Y-protection circuit |
| Application range | lightning protection zone concept at interfaces 1–2 and higher |
| Device protection | for electronic devices |
| Socket type | grounded socket outlet |
| Number of poles | two-pole |
| SPD according to EN 61643-11 / IEC 61643-11 | type 3 / class III |
| Nominal voltage (a.c.) (UN) | 230 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 255 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 3 kA |
| Total discharge current (8/20 µs) [L+N-PE] (Itotal) | 5 kA |
| Combination wave (UOC) | 6 kV |
| Combination wave [L+N-PE] (UOC total) | 10 kV |
| Voltage protection level [L-N] / [L/N-PE] (UP) | ≤ 1250 / ≤ 1500 V |
| Response time [L-N] (tA) | ≤ 25 ns |
| Response time [L/N-PE] (tA) | ≤ 100 ns |
| Max. mains-side overcurrent protection | B 16 A |
| Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR) | 1 kArms |
| Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 335 V / 5 sec. – Festigkeit, 440 V / 120 min. – sicherer Ausfall |
| Temporary overvoltage (TOV) [L/N-PE] (UT) – Characteristic | 335 V / 120 min. – Festigkeit, 440 V / 5 sec. – Festigkeit |
| Temporary overvoltage (TOV) [L+N-PE] (UT) – Characteristic | 1200 V + UREF / 200 ms – safe failure |
| Fault indication | red light |
| Operating state indication | green light |
| Number of ports | 1 |
| Operating temperature range (TU) | -25 °C ... +40 °C |
| Wire cross-sectional area | screwless double terminals up to 2.5 mm2 each, also suitable for through-wiring |
| For mounting on | retaining ring (Ø60 mm) for installation into 32 mm deep switch boxes |
| Enclosure material | thermoplastic, UL 94 V-2 |
| Place of installation | indoor installation |
| DELTA Profil line | titanium white |
The DEHN NSM PRO TW (manufacturer number 924335) is a two-pole surge protector, specifically designed as a protective earth socket with integrated surge protection circuitry for installation in electrical installation systems. It protects electronic devices from transient overvoltages caused by lightning strikes, network switching operations, or other electrical disturbances. The protector is classified as Type 3 according to the standard EN 61643-11, qualifying it for use at interfaces in the lightning protection zone concept from Zone 1 to Zone 2 and beyond. The integrated monitoring device enables continuous testing of the system's functionality, while the disconnection mechanism safely disconnects the protector from the network in case of failure to prevent hazards.
Applications
The NSM PRO TW is intended for use in electrical installations containing sensitive electronic devices, such as IT systems, communication systems, household appliances, or industrial controls. It is typically installed at the interfaces between lightning protection zones 1 and 2, where the risk of overvoltage is particularly high. The protection circuitry is designed for installation in standard socket boxes and is compatible with common installation systems.
Functions and Equipment in Detail
The protector features a confusion-proof Y-protection circuitry, ensuring correct and unambiguous assignment of protective conductors. This design minimizes the risk of incorrect connections and increases operational safety. The integrated monitoring device checks the status of the protector and signals any loss of function. The disconnection mechanism ensures that the protector is disconnected from the network in case of failure, preventing hazards due to faulty protection function. The socket is designed as a protective earth socket, enabling the use of devices with protective earth conductors.
Technology Explained Simply
The NSM PRO TW operates on the principle of a surge protector, which diverts excess voltage in the network through a discharge resistor or capacitor to protect sensitive devices. The Y-protection circuitry ensures that the protective earth conductors (PE) and phase conductors (L, N) are correctly and unambiguously connected, increasing reliability. The monitoring device continuously checks electrical parameters and can trigger a visual or electrical signal in case of failure. The disconnection mechanism is a mechanical component that disconnects the protector from the network in case of failure to prevent hazards.
Compatibility and Accessories
The protector is designed for use in electrical installation systems and can be installed in standard socket boxes. It is intended for use in the lightning protection zone concept at interfaces 1–2 and higher. The use with other DEHN products is not explicitly mentioned; however, since EN 61643-11 is a standard for surge protection devices, its use in combination with other Type 3 devices is possible.
Installation and Mounting
Installation is carried out in standard electrical installation systems, with the protector mounted in a suitable socket box. Installation must comply with applicable regulations and standards, particularly EN 61643-11. The Y-protection circuitry must be correctly connected to ensure the confusion-proof function. Installation should be performed by a qualified electrician.
Operational Advantages
The NSM PRO TW offers high safety through the integrated monitoring and disconnection mechanism, enabling early detection of damage. The confusion-proof Y-protection circuitry reduces the risk of incorrect connections and increases reliability. The installation solution as a protective earth socket allows direct use for electronic devices without additional adapters or extensions. The Type 3 classification according to EN 61643-11 makes it suitable for use at sensitive interfaces in the lightning protection concept.