| General |
| Transient discharge current (10/350 µs) | 100 kA |
| Transient discharge current (8/20 µs) | 100 kA |
| Temporary discharge current (16.7 Hz, 50 Hz, 60 Hz) | 850 Aeff (bis 200 ms) *1), 500 Aeff (bis 1s) |
| Long-duration discharge current (16.7 Hz, 50 Hz, 60 Hz) | 45 Arms (permanently) *2) |
| Transient limiting voltage (up to 1 ms) | ≤ 1.25 kV |
| Temporary limiting voltage (a.c.rms) (1 ... 20 ms) | ≤ 940 V (1 kV as per German AfK recommendation no. 3) |
| Temporary limiting voltage (a.c.rms) (20 ... 100 ms) | ≤ 660 V (1 kV as per German AfK recommendation no. 3) |
| Temporary limiting voltage (a.c.rms) (100 ... 200 ms) | ≤ 400 V (1 kV as per German AfK recommendation no. 3) |
| Long-duration limiting voltage (a.c.rms) ( 200 ms) | max. 50 V (adjustable 3 to 50 V) *3) |
| Frequency range (a.c.) | 16.7 Hz, 50 Hz, 60 Hz |
| Max. permissible voltage (d.c.) in discharge mode | + 24 V DC |
| Max. leakage current in non-discharge mode Tamb = 20 °C | max. 500 µA |
| Voltage supply (internal) | by external voltage; 9 V battery integrated |
| Voltage supply (external, optional) | 9 ... 32 V d.c., min. 0.5 A |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Terminal 1, 2 | M10 screw terminals, cross-sectional area of 35 to 50 mm² *4) |
| PE terminal | M8 (external) |
| Enclosure material | painted sheet steel, RAL 7035, inspection door with safety glass |
| Degree of protection | IP 65 |
| Digital output / type of contact | make contact |
| Switching capacity (AC) (digital OUT) | max. 230 V / max. 0.6 A |
| Switching capacity (DC) (digital OUT) | max. 220 V / max. 2 A / max. 60 W |
| Digital input / type of contact | make contact |
| Contact data (digital IN) | max. 9 V / 1 mA / 100 ohms |
| Cross-sectional area of the signal lines | max. 2.5 mm2 solid / flexible |
| Battery | 9 V block battery, lithium |
| Dimensions | 400 x 300 x 150 mm |